Running AFMS Learning Mode
Before Starting Learning Mode
For valid results, first ensure that:
l
The parameters are set correctly. (See
Setting AFMS Parameters
on page 4.)
l
The sensors are calibrated. (See
Calibrating the AFMS's Sensors
on page 6.)
l
The supply air fan is running at a normal, steady rate (without hunting or sporadic spikes).
l
If the unit has a heat recovery wheel, it is turned off.
l
If any heating or cooling sources are located upstream of the MATsensor, they are turned off.
l
If the unit has a bypass damper, it is set to 100% open.
Checking Learn Ready Status
1.
Go to AFMS, then select the Device Name of the AFMScontroller.
2.
Select the Learn tab.
3.
Take note whether Learn Ready reports READY or NOTREADY.
Interpreting Learn Ready Status
If READY is reported, you may manually start Learning Mode. (Continue to
Manually Starting Learning Mode
on page 8.)
If NOTREADY is reported:
l
Check Sensor Fault. If FAULTis reported, fix any faults found.
Note: Go to Monitor to find more detailed information on faults. (See
Monitoring with an AFMS
on
page 12.)
l
Ensure that Learn Damper Span has completed.
Note: (Under Configure,) Learn Damper Span must currently be OFF, and Damper Span Learned must
report LEARNED.
l
Mixed Air Temp Low Limit Control may be ACTIVE. If that is the case, continue to
Enabling Learning
Mode to Auto Start
on page 8.
Note: Go to Monitor to find Mixed Air Temp Low Limit Control. Go to Configure to find Enable Low Limit
and Low Temp Limit. (See
Setting AFMS Parameters
on page 4 for important guidance on Low Limit.)
KMC AFMS Commander Application Guide 7 AG230215A