Calibrating the AFMS's Sensors
1.
Go to AFMS, then select the Device Name of the AFMScontroller.
2.
Select the Tune tab.
3.
Under Offset for Supply Air Flow, enter the CFM offset (determined by a TABtechnician) for the supply air
pressure transducer.
4.
Under Multiplier for Supply Air Flow, enter the multiplier (determined by a TABtechnician) for the supply air
pressure transducer.
5.
Under Offset for Outside Air Temp, Return Air Temp, and Mixed Air Temp, enter the °F offsets (determined
by a TABtechnician) for the outside, return, and mixed air temperature sensors.
6.
Select Save.
Note: For more information on the AFMS's sensors, see the
Airflow Measurement System Selection
Guide,
found on any AFMScontroller's product page.
Continue to
Running AFMS Learning Mode
on page 7.
KMC AFMS Commander Application Guide 6 AG230215A