Installation Guide

Calibrating the AFMS's Sensors
1.
Go to AFMS, then select the Device Name of the AFMScontroller.
2.
Select the Tune tab.
3.
Under Offset for Supply Air Flow, enter the CFM offset (determined by a TABtechnician) for the supply air
pressure transducer.
4.
Under Multiplier for Supply Air Flow, enter the multiplier (determined by a TABtechnician) for the supply air
pressure transducer.
5.
Under Offset for Outside Air Temp, Return Air Temp, and Mixed Air Temp, enter the °F offsets (determined
by a TABtechnician) for the outside, return, and mixed air temperature sensors.
6.
Select Save.
Note: For more information on the AFMS's sensors, see the
Airflow Measurement System Selection
Guide,
found on any AFMScontroller's product page.
Continue to
Running AFMS Learning Mode
on page 7.
KMC AFMS Commander Application Guide 6 AG230215A