Specifications
GENERAL SPECIFICATIONS
C US
Klimaire Model No.
KUIM012-H2 KUIM018-H2 KUIM024-H2
V-ph-Hz
208~230-1-60 208~230-1-60 220-1-60
Capacity Btu/h
12.000 18.000 25.000
SEER
19 16 17
Capacity Btu/h
12.400 18.400 26.000
HSPF
9,1 8,5 8,9
Indoor fan motor Qty n
1 1 1
Speed(Hi/Med/Lo) r/min
1300±20 1300±20 1300±20
Indoor unit Dimension (WxDxH) in
39" x 26" x 8" 39" x 26" x 8" 42" x 26"-9/16 x 9"-1/4
Packing (WxDxH) in
42"-29/32 x 29"-5/16 x 11"-11/16 42"-29/32 x 29"-5/16 x 11"-11/16 45"-1/16 x 29"-23/32
Net/Gross weight lb
48.4 / 61.6 52.8 / 66 55 / 66
psig
340 340 340
in
Φ 1" Φ 1" Φ 1"
Refrigerant piping Liquid side/Gas side in
1/4" / 1/2" 3/8" / 5/8" 3/8" / 5/8"
RG05F2/BGEU1 RG05F2/BGEU1 RG05F2/BGEU1
Cooling ºF
?63 ?63 ?63
Heating ºF
?86 ?86 ?86
Operation
temperature
Cooling
Heating
Power supply
Design pressure
Drainage water pipe diameter
Controller
L
H
KUIM Indoor Units
Light Commercial Series
Remarks:1.The above design and specifications are subject to change without prior notice for product improvement.
2.The values given in the table for the noise level reflect the levels in anechoic chamber.
Indoor Unit
Indoor unit model number KUIM036-H2 KUIM048-H2
Power supply V/ph/Hz
208-230/1/60 208-230/1/60
Cooling
Capacity Btu/h
36.000 48.000
SEER
—
15 16
Heating
Capacity Btu/h
36.000 49.000
HSPF
—
9,0 10,0
Indoor fan motor
Quantity n
1 2
Speed (Hi/Med/Lo) rpm
1300/1150/800 1320/1200/1120
Dimension (WxDxH)
in
50.59x26.57x9.25 64.96x26.57x9.25
Indoor unit
Packing (WxDxH)
in
53.54x29.72x12.32 67.91x29.72x12.32
Net/Gross weight lb
66.14/77.16 83.78/97
Design pressure
psig 550 / 340 550 / 340
Drainage water pipe diameter in
OD Ф1" OD Ф1"
Refrigerant piping
Liquid /Gas in
3/8" / 5/8" 3/8" / 5/8"
Controller —
RG05F2/BGEU1 RG05F2/BGEU1
Room temperature
Cooling
Heating
℉ 62~90 62~90
℉ 32~86 32~86