Installation Manual
 Page 27  
6.  Place flaring tool onto the form.
7.  Turn the handle of the flaring tool clockwise 
until the pipe is fully flared.
8.  Remove the flaring tool and flare form, then 
inspect the end of the pipe for cracks and 
even flaring.
Step 4: Connect pipes
When connecting refrigerant pipes, be careful 
not to use excessive torque or to deform the 
piping in any way. You should first connect the 
low-pressure pipe, then the high-pressure pipe.
MINIMUM BEND RADIUS
When bending connective refrigerant piping, 
the minimum bending radius is 10cm. See  Fig 
5.6 .
≥10cm (4in)Radius
TORQUE REQUIREMENTS
Outer Diameter of Pipe (mm) Tightening Torque (N•cm) Add. Tightening Torque (N•m)
Ø 6.35 (Ø 0.25”) 1,500 (11lb • ft) 1,600 (11.8lb • ft)
Ø 9.52 (Ø 0.375”) 2,500 (18.4lb • ft) 2,600 (19.18lb • ft)
Ø 12.7 ( Ø 0.5”) 3,500  (25.8lb•ft) 3,600  (26.55lb•ft)
Ø 16 ( Ø 0.63”) 4,500  (33.19lb•ft) 4,700  (34.67lb•ft)
 DO NOT USE EXCESSIVE TORQUE
Excessive force can break the nut or damage the refrigerant piping. You must not exceed torque 
requirements shown in the table above.
Instructions for Connecting Piping to 
Indoor Unit
1.  Align the center of the two pipes that you will 
connect. See  Fig. 5.7 .
Indoor unit tubing Flare nut Pipe
2.  Tighten the flare nut as tightly as possible by 
hand.
3.  Using a spanner, grip the nut on the unit 
tubing.
4.  While firmly gripping the nut on the unit 
tubing, use a torque wrench to tighten the 
flare nut according to the torque values in the 
Torque Requirements  table below. Loosen 
the flaring nut slightly, then tighten again.
Fig. 5.6
Fig. 5.7
Fig. 5.8
Refrigerant 
Piping 
Connection 










