V. ELECTRICAL INSTALLATION
WARNING: REMOVE POWER FROM THE UNIT BEFORE INSTALLING, REMOVING OR MAKING
ADJUSTMENTS
GENERAL SAFETY
When using electrical equipment, you should always follow basic safety precautions, including the following:
• Theinstallation/wiringofthisproductmustcomplywithallnational,federal,state,municipal,andlocal
codes that apply.
• Properlygroundtheenclosuretoanadequateearthground.
• Donotmodifyanyfactorywiring.Connectionsshouldonlybemadetotheterminalsdescribedinthis
section.
• Allconnectionstotheunitmustuseconductorswithaninsulationratingof300Vminimum,ratedfor
105C,aminimumammabilityratingofVW-1,andbeofappropriategaugeforthevoltageandcurrent
required (see specs).
• Donotallowmoisturetoentertheelectronicsenclosure.Conduitshouldslopedownwardfromthe
housing. Install drip loops and seal conduit with silicone rubber product.
DISCONNECT REQUIREMENTS FOR PERMANENTLY INSTALLED EQUIPMENT
A dedicated disconnecting device (circuit breaker) must be provided for the proper installation of the unit. If
independent circuits are used for power input, individual disconnects are required. Disconnects must meet the
following requirements:
• Locatedincloseproximitytothedevice
• Easilyaccessibletotheoperator
• Appropriatelymarkedasthedisconnectforthedeviceandassociatedcircuit
• Sizedappropriatelytotherequirementsoftheprotectedcircuit(SeeSpecications)