V. ELECTRICAL INSTALLATION
WARNING: REMOVE POWER FROM THE UNIT BEFORE INSTALLING, REMOVING OR MAKING
ADJUSTMENTS
GENERAL SAFETY
When using electrical equipment, you should always follow basic safety precautions, including the following:
• Theinstallation/wiringofthisproductmustcomplywithallnational,federal,state,municipal,andlocal
codes that apply.
• Properlygroundtheenclosuretoanadequateearthground.
• Donotmodifyanyfactorywiring.Connectionsshouldonlybemadetotheterminalsdescribedinthis
section.
• Allconnectionstotheunitmustuseconductorswithaninsulationratingof300Vminimum,ratedfor
105C,aminimumammabilityratingofVW-1,andbeofappropriategaugeforthevoltageandcurrent
required (see specs).
• Donotallowmoisturetoentertheelectronicsenclosure.Conduitshouldslopedownwardfromthe
housing. Install drip loops and seal conduit with silicone rubber product.
DISCONNECT REQUIREMENTS FOR PERMANENTLY INSTALLED EQUIPMENT
A dedicated disconnecting device (circuit breaker) must be provided for the proper installation of the unit. If
independent circuits are used for power input, individual disconnects are required. Disconnects must meet the
following requirements:
• Locatedincloseproximitytothedevice
• Easilyaccessibletotheoperator
• Appropriatelymarkedasthedisconnectforthedeviceandassociatedcircuit
• Sizedappropriatelytotherequirementsoftheprotectedcircuit(SeeSpecications)