User Manual
9
ORB180213 Rev. A
TO OBTAIN A CURRENT COUNT READING – FOR EARLIER ORB SOFTWARE VERSIONS
1. LogintotheORBnormally
2. Click ‘Realtime View’ from the left side navigation on the Main Menu screen
3. Verifythatthetimevalueisve(5)secondsorless.
4. Record the ADC value and the weight or level of the material in the vessel.
5. Click Main Menu
6. Add or remove material from the vessel
7. Click ‘Realtime View’ from the left side navigation on the Main Menu screen
8. Verifythatthetimevalueisve(5)secondsorless.
9. Record the ADC value and the weight or level of the material in the vessel.
TO SET UP AN INPUT CARD
1. LogintotheORBnormally
2. Choose Manage Devices
3. Click on one of the 4-20 mA names listed
4. In the ‘Settings’ column, if desired, change the name to a recognizable description.
5. Changeunitsasdesired.Anynameorvaluecanbelistedinthiseld.
6. Typein‘LowSpanCounts’–thisisthevaluepredeterminedasshowninthestepsabove.LowSpan
Counts is the value the device equates to empty (or full).
7. Typein‘HighSpanCounts’–thisisthevaluepredeterminedasshowninthestepsabove.HighSpan
Counts is the value the device equates to full (or empty).
8. Typein‘HighSpan’–thisisthevaluethevesselhadwhenthecountswererecorded
9. Typein‘LowSpan’–thisisthevaluethevesselhadwhenthecountswererecorded.
10. Click ‘Update with these Settings’