Owner manual

7
www.kistlermorse.com
97-1076-01 Rev. B
1. Remove the Junction Box cover.
2. Route the 3-conductor cable through the tting into the junction box farthest from the controller.
3. Connect the wires from the cable to the TB3 terminal in the Junction Box.
Black wire to B Terminal
White wire to W Terminal
Red wire to R Terminal
4. Connect the cable shield wire to the Shield Terminal between TB1 and TB2.
NOTE: The shield terminal will not connect to anything; be sure to connect on the device side though.
5. Route the cable through the conduit/cable tray to the next Junction Box.
6. Estimate the required length of cable to the terminal strip, allowing for a little extra for strain relief. Cut
the excess cable.
7. Connect wires from the cable tothe TB1 Terminal in the Junction Box - see Step 3 above.
8. Route another 3-conductor cable through the tting into this Junction Box and attach wires to the TB2
Terminal - see Step 3 above.
9. Repeat until all vessels are wired together.
10. Route the cable from the last Junction Box through the conduit/cable tray to the controller. Refer to the
controller manual for wiring diagarams required to wire the Junction Box to the controller. One vessel
takes up one channel in the controller; the channel shows the average value from all the sensors on the
vessel supports.
FROM VESSEL LEGS
LOAD DISC CABLES LOAD DISC CABLES
FROM VESSEL LEGS
TO SIGNAL PROCESSOR
OR OTHER J-BOX
SENSOR A
TB3
TB2
SENSOR D
12RW
B
TP1
3RW
MADE IN USA
ASSY 63-1170-
SENSOR B
B
SENSOR C
REV.
RWRW
R1
W BRB1
R2
NO STANDARDIZATION
R SHLD1
B13
TB1
WB
1
12
SENSOR D
RWB
TP1
TB2
3RW
MADE IN USA
SENSOR B
ASSY 63-1170-
SENSOR C
REV.
W RBRW
R1
TB3
R BW
SENSOR A
B1
R2
NO STANDARDIZATION
SHLD1
B13
R
TB1
WB
1