Product Manual
Page 12
>25Aac and <27Aac 10 Adc >21Aac and <26Aac 15 Adc
>20Aac and <25Aac 20 Adc >16Aac and <21Aac 35 Adc
<20Aac 40 Adc <16Aac 55 Adc
Manufacturing Default Setting
Fd Reset all settings to manufacturing default settings
(40A for IC121040 or 55A for IC122055, In1, AL1, SdL, Flo, Cb3)
Understanding the Charger De-rating Current:
The charger current will be de-rated when the environment temperature reaches 60
°C (140 °F) or the internal temperature reaches the pre-set values.
Unit De-rated Values
>90°C (194°F) Maximum charger will de-rated
to half
>95°C (203°F) Charger current reduced to 5A
Internal Temperature
<85°C (185°F) Charger current recover back
to set value
>60°C (140°F) Charger current reduced to 5A Environment Temperature
>55°C (131°F) Charger current recover back
to set value
Enter Function Menu for unit setting:
To enter unit Function Menu, press and hold “Power” and “Select” button together for about 5
seconds until a beep is sounded.
When you are in Function Menu:
• Press ‘Power’ button for 1 second to toggle between different Functions Menu like ‘Cu’, ‘In’,
‘AL’, ‘Sd’, ‘bAt’, ‘Cb’ and ‘Fd’ etc.
• Press ‘Select’ button for 1 second to enter Individual Function Set Menu and you can
make change to the settings.
• The unit will EXIT the Main Menu automatically if ‘Power’ and ‘Select’ buttons is not trigger
for more than 5 seconds.
When you are in Individual Function Set Menu:
• Press ‘Select’ button for 1 second to toggle between different setting values.
• Press ‘Select’ button for 5 seconds to set selected setting and exit to next Main Menu
See more details on flow chart below.