Product Manual

Page 15
be modified, press and hold the Menu/Set button for 5 seconds and the set parameter will flash
on the display. Use the or button to scroll through the available settings. Once the desired
setting is chosen, press and hold the Menu/Set button until a beeping sound occur and the new
setting is saved.
- Press Escape button once to return back to Normal Operation. (If none of the button is
triggered for about 5 seconds, display will also return back to Normal Operation.
Unit Setting Function Chart
Unit Setting
Display
Description and Available Setting
Inverter
: Use as Inverter only. No By-Pass functions.
(Default): Auto Backup. Inverter automatically turns ON when AC Blackout.
: Manual Backup. When AC Blackout occurs, Inverter has to be manually
turned ON by using the ‘Power’ button’ on either the Display panel or the
‘Power’ button on the Main unit
: Inverter function is disabled. No AC backup when AC Blackout.
Load Sense
(Default): Continuous AC Output when inverter is ON
10 : Continuous AC Output when inverter is ON and AC load is > 10W
15 : Continuous AC Output when inverter is ON and AC load is > 15W
20 : Continuous AC Output when inverter is ON and AC load is > 20W
25 : Continuous AC Output when inverter is ON and AC load is > 25W
Battery Low
Disconnect
10.5*
Battery Low Disconnect Voltage selectable ranges is 10.5 - 12.0V (0.1V steps) *
(Default voltage is set to 10.5V*)
Battery Low
Warning
11.0*
Battery Low Warning Voltage selectable ranges is 11.0 - 12.5V (0.1V step)*
(Default voltage is set to 11.0V*)
Battery Low
Recovery
12.0*
Battery Low Recovery Voltage selectable ranges is 11.5 - 13.0V (0.1V step)*
(Default voltage is set to 12.0V*)
Audible
Buzzer
(Default): Buzzer is enabled. Unit buzzes when Warning or Error occurs.
: Buzzer is disabled. Unit does not buzz when Warning and Error occur.
AC Charger
(Default): AC Charger is enabled. Charge battery when AC Input is available.
: AC Charger is disabled. No battery charging when AC Input is available.
Battery Type
(Default): GEL Battery, default Bulk Charge/Float Voltage is 14.2V/13.8V*
: AGM Battery, default Bulk Charge/Float Voltage is 14.3V/13.4V*
: Flooded Battery, default Bulk Charge/Float Voltage is 14.4V/13.5V*
: Lithium Battery, default Bulk Charge/Float Voltage is 13.9V/13.5V*
: Program, default Bulk Charge/Float Voltage is 13.8V/13.2V*
: Power Supply Mode, Default Power Supply Voltage 13.8V*
Bulk Current
100
12V/3000W Models: Selectable Ranges 100A, 80A, 60A, 40A, 25A (Default 100A).
12V/2000W Models: Selectable Ranges 80A, 60A, 40A, 20A, 10A (Default 80A).
24V/3000W Models: Selectable Ranges 50A, 40A, 30A, 20A, 10A (Default 50A).
24V/2000W Models: Selectable Ranges 40A, 30A, 20A, 10A, 5A (Default 40A).
Bulk/Absorpt-
ion Voltage
14.2*
Bulk/Absorption voltage is based on the battery type chosen. All battery types have
selectable ranges of 13.8 14.8V*. (Default on GEL Battery is 14.2V*)
Absorption to
Float Current
10
12V/3000W Models: Selectable Range: 20A, 15A, 10A, 5A, 2A (Default 10A).
12V/2000W Models: Selectable Range: 15A, 10A, 8A, 4A, 2A (Default 8A).
24V/3000W Models: Selectable Range: 8A, 6A, 5A, 3A, 2A (Default 5A).
24V/2000W Models: Selectable Range: 6A, 5A, 4A, 3A, 2A (Default 4A).
Float Voltage
13.8*
Float voltage is based on the battery type chosen. All battery types have selectable
ranges of 13.0 14.0V*. (Default on GEL Battery is 13.8V*)
Recharge
Voltage
12.8*
Battery Recharge Voltage Selectable Range: 12.8 to 14.0V (0.1V step)* (Default on
GEL, AGM, Flooded, PGM battery setting is 12.8V* and Li setting is 13.2V).
Battery
Temperature
: High > 35 °C
(Default): Normal 15 - 35°C
: Low < 15°C
AC Input
Source Circuit
Breaker
30
120 Vac Models: Range: 30A, 20A, 15A (Default 30A).
230 Vac Models: Range: 4,6,8,10,12,13,14,16A,
(Default 16A on EU, 13A on UK and AU).
Factory
Default
Select to reset all settings to default.
* for 24 V Models (BIC2430050, BIC2420040, BIC2430050i, BIC2420040i), all the voltage values are doubled.