Product Manual


Page 13
E01 Unit shutdown due to low AC Input
(< 85 +/- 5Vac)
Check AC input source. The unit will
automatically recover when the AC Input
voltage return to > 108 +/-5Vac
E02 Unit shutdown due to high AC
Input (>270 +/- 5Vac)
Check AC input source. The unit will
automatically recover when the AC Input
voltage return to < 260 +/-5Vac
E03 Battery is connected backwards Check all battery connections
E04 Charger Internal temperature is
too high and unit has shutdown.
Unit will automatically recover
when the unit cools down.
The ventilation of the unit is blocked or
the environmental temperature is high.
Reduce charging current or improve the
ventilation near the unit.
E05 Inlet temperature is high >60°C
(140°F) and unit has shutdown.
Unit will automatically recover
when inlet temperature is reduced
to <45°C (113°F).
Check environmental temperature.
Improve the ventilation around the unit.
E06 High battery temperature >70 °C
(158°C) is sensed by the BTS. The
unit will shutdown. Unit will
automatically recover when battery
temperature has reduced to 60°C
(140°F).
Check battery, charger setting and the
environment the charger is in.
E07 Low battery temperature < -25°C
(-13°F) is sensed by the BTS. The
unit will shutdown. Unit will
automatically recover when battery
temperature reaches -20°C (-4°F).
It is not recommended to charge the
battery at extreme low temperatures.
E08 DC Output fuses are brown. Check battery connection and replace
fuse with the same type and rating.
E09 Unit shutdown due to high battery
voltage (> 17Vdc). Unit will
automatically recover when battery
temperature reduced to 16Vdc.
Check battery and charger setting.
Check also if there is any other DC
supply connected to the battery banks.