User Manual
Preset Single Register
Description:
By this command a single register can be written.
Request Telegram
ADR FNR REGSTA REGNUM CRC
6 MSB LSB MSB LSB MSB LSB
Response Telegram
ADR FNR REGADR DATA CRC
6 MSB LSB MSB LSB MSB LSB
ADR ............ module address (hex 00..7F)
FNR ............ function number (hex 06)
REGADR ..... address of the register to be written
DATA …….... data word (hex 0000…FFFF)
CRC ............ check sum
CRC polynomial: u
15
+ u
13
+ 1
CRC start value: hex FFFF
Hardware Manual COMBILOG 1022
132