pointer setting. If there is no further communication within 1
minute, password release is deleted.
For passwords, only capital letters and numbers are accepted.
char meaning length range
# start delimiter for request telegram with
check sum
1 ASCII "#"
> start delimiter for response telegram
with check sum
1 ASCII ">"
$ start delimiter for request telegram
without check sum
1 ASCII "$"
= start delimiter for response telegram
without check sum
1 ASCII "="
<cr> end delimiter (carriage return) 1 hex 0D
ACK positive acknowledge 1 hex 06
NAK negative acknowledge 1 hex 15
aa destination address 2 ASCII
"01".."7F"
cc check sum 2 ASCII
"00".."FF"
kk channel number
- for internal channels
- for external channels
2 ASCII
"01".."20"
"80".."BB"
v..v device identification 28 ASCII - string
s..s device information 28 ASCII - string
z..z status information 12 ASCII - string
i..i channel information 32 ASCII - string
d..d channel value max. 8 ASCII - string
b..b events variable ASCII - string
e error code 1 ASCII "1".."2"
t..t date and time 12 ASCII - string
n..n measuring rate and averaging interval 7 ASCII - string
a..a number of events 5 ASCII - string
p..p password max. 8 ASCII - string
Table 11.10 Explanation of the command characters in the ASCII-pro-
tocol
Hardware Manual COMBILOG 1022
112