User Manual
IMPORTANT: Turn off power before
installing or removing connector.
Product to be used in accordance with
local and national codes.
1. Strip wires 5/8” (15.9mm).
2. Pre-twisting not required. Hold
stripped wires together with ends of
insulations even. Lead stranded wires
slightly.
3. Align any frayed strands or
conductor.
4. Firmly push wire into connector and
screw connector clockwise onto wire
until tight.
To be sold only with installation instructions.
SKU# Selling Unit
68205 Bag of 10
68210 Box of 100
68230 Canister of 300
68270 Box of 5,000
68290 Drum of 25,000
Max. Voltage: 600V max. building wire
(1000V max. signs or luminaries)
Connector Size: 1 11/32” x 5/8”
Wire Type: Copper/Copper
Wire Range: Min 2 #18/Max 2 #8
Temperature Rating: 105°C (221°F)
INSTALLATION INSTRUCTIONS
PRODUCT SPECIFICATIONS
AND MEASUREMENTS
www.kinginnovation.com
(P) 800.633.0232
(F) 636.519.5410
Measurements (Inches):
A - 1.350
B - 0.626
C - 0.650
Gorilla Nuts
®
Cushion Grip Wire Connectors
U.S. Pat. 9,231,313, 7,560,645, 8,067,692
8,525,026 and additional Patents Pending
apply. All other trademarks, U.S. and Foreign
Patents Pending apply. All Rights Reserved.
2 #8 1, 2, 3, 4 or 5 #12
1 #10 w/1 or 2 #12 1, 2 or 3 #10
1 #10 w/1, 2, 3 or 4 #18 2 #10 w/1 #12
2 #10 w/2 #16 2 #18
Selected 600V Wire Combinations
Contact factory for a complete list of wire