Specification
Architectural and Engineering
Specifications
The LED strobe light shall be Kidde Unit SLED177i or
approved equal. It shall be powered by a 120VAC, 60Hz
source. The temperature operation range shall be between
32°F and 120°F (0°C and 49°C). The LED strobe light can
be installed on any standard single gang electrical box, up
to a 4” octagon junction box. The electrical connection
(to the device) shall be made with a plug-in connector. A
maximum of 24 Kidde devices can be interconnected in a
multiple station arrangement. The interconnect system
must not exceed the NFPA (National Fire Protection
Association) limit of 18 initiating devices (Smoke, heat,
CO, etc) interconnected. With 18 initiating devices, it is
still possible to interconnect 6 strobe lights and/or relay
modules.
The unit can be directly interconnected with Kidde Safety
3-wire Smoke, Heat and CO alarms. It will produce an
intermittent strobe flash pattern (approximately 4 flashes,
followed by approximately 5 seconds off) when triggered by
a Carbon Monoxide alarm, and a flash every second when
triggered by a smoke or heat alarm. The unit shall at a mini-
mum meet the requirements of UL1971, NFPA72, the State
of California Fire Marshall, NFPA101 (One and two family
dwellings, Federal Housing Authority (FHA), Housing and
Urban Development (HUD), Americans with Disabilities Act
(ADA). The unit shall be UL Listed.
Installation of Strobe Light
The LED strobe light should be installed to comply with all
local codes having jurisdiction in your area, Article 760 of
the National Electric Code, and NFPA 72. Make certain all
devices are wired to a single, continuous (non-switched) power
line, which is not protected by a ground fault interrupter. A
maximum of 1000 ft. of wire can be used in the interconnect
system. Light output gradually decreases as viewing angle is
increased. Consult chart in users guide to determine the best
location for the strobe light installation.
120VAC Dual Mode LED Strobe Light
for the Hearing Impaired
Model Number SLED177i
Technical Specifications
Model: SLED177i
Power Source: 120VAC, 60HZ
Electrical Rating: 96 - 132 VAC, 60HZ, 630 mA max
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Flash Rate: Fire: Constant 1 flash per second
CO: Intermittent 1 flash per second
(4 flashes, 5 seconds off)
Light Output 177 Candela
Size: 5.6” in diameter x 3” depth
Weight: .85 lb
Interconnects: Up to 24 Kidde devices of which 18
can be initiating devices.
Warranty: 10 year limited warranty
P/N: KL-SLED177i sheet rev. 08-2014
Distributed by:
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Ordering Information
Ordering Pack Pack Dimensions Cartons/
Number UPC I2F5 Config. Quantity (w x d x h inches) Weight Pallet
SL177i 0-47871-24003-6 200-47871-24003-0 BOX 6 6.2 x 10.4 x 6.2 2.95 168
Not for sale by individual unit