When mounting an alarm on the ceiling, locate it at a minimum
of 4” (10cm) from the side wall (see figure 1).
When mounting the alarm on the wall, use an inside wall with
the top edge of the alarm at a minimum of 4” (10cm) and a
maximum of 12” (30.5cm) below the ceiling (see figure 1).
Put smoke alarms at both ends of a bedroom hallway or large
room if the hallway or room is more than 30 ft (9.1 m) long.
Install Smoke Alarms on sloped, peaked or cathedral ceilings at
or within 3ft (0.9m) of the highest point (measured horizontally).
NFPA 72 states: “Smoke alarms in rooms with ceiling slopes
greater than 1 ft in 8 ft (.3m in 2.4m) horizontally shall be locat-
ed on the high side of the room.” NFPA 72 states: “A row of
alarms shall be spaced and located within 3 ft (0.9m) of the
peak of the ceiling measured horizontally” (see figure 3).
2. LOCATIONS TO AVOID
In general alarms should not be located:
In the garage. Products of combustion are present when you
start your automobile.
Less than 4” (10cm) from the peak of an “A” frame type ceiling.
In an area where the temperature may fall below 40ºF or rise
above 100ºF, such as garages and unfinished attics.
In dusty areas. Dust particles may cause nuisance alarm or fail-
ure to alarm.