PRODUCT DESCRIPTION
The remote accessory is available with only the single gang remote indicator/control (591 Series), or with the addition of a single gang strobe
assembly (592 Series), or as an optional field upgrade kit for existing installed 591 Series (593 Series).
All versions are compatible with standard Decora style cover plates (base color choice plate included).
The indicator/control assembly provides
• Visual indication of detector Pilot, Trouble and Alarm Functions
• Selectable audible indication of Alarm, Trouble or both
• Buzzer Silence function, with “ringback” following condition correction
• Lamp/Buzzer test function
• Key-Operated detector Test and Reset functions
• Lever-operated “No-Tools” terminal block
• Port for plugging in Strobe Assembly
The strobe assembly provides visual indication of alarm conditions, and
is connected to the indicator/control assembly via the provided connector
(observing connector polarity).
**
NOTE: The strobe and audible buzzer features are not ADA
compliant, and not intended for life safety notification or evacuation
purposes (public mode). These functions are for duct smoke detector
status indication only (private mode).
STROBE CONNECTION
To install the Strobe module, simply plug the provided con-
nector onto the pins as indicated on the rear of the indica-
tor/control module. Snap the strobe lens into the cover
plate, and install cover plate following completion of remote
module wiring.
AUDIBLE BUZZER CONFIGURATION
There are two jumpers located on the rear of the indicator/control assembly. To enable audible
buzzer operation for Alarm or Trouble conditions, simply leave the jumpers in place. To disable either
or both functions, remove the appropriate jumper(s).
SILENCE AND RINGBACK FUNCTIONS
On the occasion where an audible alarm or trouble condition needs to be silenced while the detector condition is
inspected and remedied, the indicator/control module provides a silence function. The slide switch located on the
front of the module is pushed DOWN to activate the silence function.
Upon correction of the notified condition, the silenced buzzer will resume sounding. This the ringback feature
which serves as a reminder to reset the silence switch to the “normal”, UP position.
Note that the strobe module, when used, will not stop operating when the silence function is engaged.
DUCT SMOKE DETECTOR REMOTE ACCESSORY
INSTALLATION GUIDE
191 E. North Avenue Carol Stream, IL 60188 USA
Tech. Service Phone: +1 800 445 8299 E-mail: technicalservice@invensys.com www.invensys.com
INST APD0340 A060829
A COPY OF THESE INSTRUCTIONS SHOULD BE LEFT WITH THE EQUIPMENT UNTIL INSTALLATION BY ALL TRADES IS FULLY COMPLETE.
FOLLOWING FINAL INSPECTION, A COPY SHOULD BE LEFT WITH THE OWNER/USER.
NOTICE: The information contained in this document is the most current available at the time of shipment of accompanying product, and is subject to change without notice. Future references should always be made
to the most current revision of this document. The information contained in all this document should be considered before installing or using the product. Any example applications shown are subject to the most cur-
rent enforced local/national codes, standards, approvals, certifications, and/or the authority having jurisdiction. All of these resources, as well as the specific manufacturer of any shown or mentioned related equipment,
should be consulted prior to any implementation. For further information or assistance concerning this product, contact Invensys. Invensys reserves the right to change any and all documentation without notice.
© Invensys Climate Controls Americas 2006
AVAILABLE ACCESSORIES FOR USE WITH
FIREX
®
DUCT SMOKE DETECTORS
REMOTE ACCESSORIES
591 Series Remote Accessory Controllers
591W Remote Indicator/Control Assembly w/ White Single Gang Cover Plate
591R Remote Indicator/Control Assembly w/ Red Single Gang Cover Plate
591S Remote Indicator/Control Assembly w/ Stainless Steel Single Gang Cover Plate
592 Series Remote Accessory Controllers with Strobe
592WC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); White Double Gang Cover Plate
592WO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); White Double Gang Cover Plate
592RC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); Red Double Gang Cover Plate
592RO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate
592SC Remote Indicator/Control Assembly w/ Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate
592SO Remote Indicator/Control Assembly w/ Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate
593 Series Remote
Accessory Strobes (as an optional field upgrade kit for existing installed 591 Controllers)
593RC Strobe Assembly (Clear Lens); Red Double Gang Cover Plate
593RO Strobe Assembly (Opaque Lens); Red Double Gang Cover Plate
593SC Strobe Assembly (Clear Lens); Stainless Steel Double Gang Cover Plate
593SO Strobe Assembly (Opaque Lens); Stainless Steel Double Gang Cover Plate
593WC Strobe Assembly (Clear Lens); White Double Gang Cover Plate
593WO Strobe Assembly (Opaque Lens); White Double Gang Cover Plate
SMOKE TEST GAS
565 Solo Aerosol Test Gas with Nozzle for 2650-760/761 Series Test Port
NOTCHED SAMPLING TUBES (2650-760/761 SERIES)
552 For duct widths of 1.0’ TO 2.5’
553 For duct widths of 2.5’ TO 5.0’
554 For duct widths of 5.0’ TO 10.0’
SAMPLING TUBES (2650-660/661, 2650-560/561 SERIES)
532 For duct widths of 1.0’ TO 2.5’
533 For duct widths of 2.5’ TO 5.0’
534 For duct widths of 5.0’ TO 10.0’
WEATHERPROOF ENCLOSURES
555 Weatherproof Enclosure for 2650-760/761 Series Detectors
590 Weatherproof Enclosure for 2650-660/661, 2650-560/561 Series Detectors
Normal
“Standby”
Mode
Silenced
Mode
ALM
TBL
Buzzer will function
on both Alarm
and Trouble conditions
ALM
TBL
Buzzer will function
on Alarm condition
only
ALM
TBL
Buzzer will function
on Trouble condition
only
ALM
TBL
Buzzer will not function
on Alarm or Trouble
conditions
REAR OF INDICATOR/CONTROL