Specification

Battery Operated Combination
Carbon Monoxide & Smoke Alarm
Part # 900-0102A
Model KN-COSM-BA
Architectural and Engineering
Specifications
The combination smoke and carbon monoxide alarm shall be Kidde
Model Number KN-COSM-BA (part number 900-0102A) or approved
equal. It shall be powered by 2 AA batteries. The unit shall incorpo-
rate an ionization smoke sensor with nominal sensitivity of 0.97 %/
ft. The CO sensor shall be of a fuel cell design and provide accuracy
of +/-20% + 15ppm. The temperature operating range shall be
between 40°F and 100°F (4°C and 38°C) and the humidity operating
range shall be 10% - 95% relative humidity, non-condensing.
The combination alarm can be installed on the surface of any wall or
ceiling following the UL/NFPA/Manufacturer’s recommended place-
ment guidelines. The alarm shall provide optional tamper resistance
that deters removal of the unit from the wall or ceiling.
The alarm shall include a test button that will electronically simulate
the presence of smoke and CO and cause the unit to go into both
modes of alarm. This sequence tests the unit’s electronics to ensure
proper operation.
The CO sensor will not alarm to levels of CO below 30 ppm and will
alarm in the following time range when exposed to the correspond-
ing levels of CO.
70 ppm CO Concentration 60 – 240 minutes
150 ppm CO Concentration 10 – 50 minutes
400 ppm CO Concentration 4 – 15 minutes
The combination alarm shall have two methods of warning for danger:
a piezoelectric horn that is rated at 85 decibels at 10 feet and a voice
warning that identifies the danger. For a CO incident, the horn will
sound in the repetitive manner -- four (4) fast beeps, a short pause,
four (4) fast beeps, a short pause. In between, the unit will announce
“Warning Carbon Monoxide!”. In a Smoke incident, the horn will
sound in the repetitive manner -- three (3) beeps, a pause, three (3)
beeps, a pause. In between, the unit will announce “Fire!”
The unit shall also indicate a low battery warning utilizing each of the
following methods: a brief alarm chirp, the voice announcement of
“Low Battery!” and the red LED will flash once per minute. The unit
shall incorporate 2 LED’s. A green LED will flash every 60 seconds in
standby condition. A red LED will flash during smoke or CO alarm,
and in error mode.
The unit shall at a minimum meet the requirements of UL 2034,
UL217, NFPA72, (chapter 11 2002 edition) The State of California Fire
Marshall, NFPA101 (One and two family dwellings) Federal Housing
Authority (FHA), Housing and Urban Development (HUD). It shall also
include a 7-year manufacturer’s limited warranty.
Technical Specifications
Unit Number: 900-0102A
Model: KN-COSM-BA
Power Source:
2 AA Battery
Sensors: Smoke: Ionization, CO: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10%-95% relative humidity
non-condensing
Size: 5.6” in diameter x 1.8” depth
Weight: 13oz
Interconnects: No
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788 www.Kidde.com
KL-900-0102A sheet rev. 11-2015
Distributed by:
5.6” 1.8”
Ordering Information
Ordering Pack Pack Dimensions Cartons/
Number UPC I 2 of 5 Config Qty (w x d x h inches) Weight Pallet
900-0102-02 7-84908-01020-9 107-84908-01020-6 CLAM PDQ (3 Units) 6.3 x 7.8 x 11.8 3.15 111
900-0102-16 7-84908-01020-9 207-84908-01020-3 CLAM Cut Case (20 Units) 16 x 23.3 x 11.9 21.5 18
21006674 7-84908-01020-9 407-84908-01020-7 CLAM Cut Case (8 Units) 8.1 x 17.6 x 11.9 8.3 36
21006974 0-47871-05296-7 BULK Bulk Pack (6 Units) 6.7 x 12.2 x 7.3 5.15 126
21007164 7-84908-01020-9 607-84908-01020-1 CLAM Display (48 Units) 16.7 x 43 x 43 57 4