Use and Care Manual
16
Wiring Instructions for AC Quick Connector Harness
 CAUTION:  Turn off the main power to the circuit before wiring the alarm.
 • For alarms that are used as single station, DO NOT CONNECT THE RED WIRE TO ANYTHING. Leave the red wire 
insulating cap in place to make certain that the red wire cannot contact any metal parts or the electrical box.
 • When alarms are hardwire interconnected, all interconnected units must be powered from a single circuit.
 • A maximum of 24 Kidde Safety devices may be interconnected in a multiple station arrangement. The intercon-
nect system should not exceed the NFPA interconnect limit of 12 smoke alarms and/or 18 alarms total (smoke, 
CO, Smoke/ CO Combination, heat, etc.). With 18 alarms interconnected, it is still possible to interconnect up to 
a total of 6 remote signaling devices and/or relay modules.
 • Figure 9-B illustrates interconnection wiring. Improper connection will result in damage to the alarm, failure to 
operate, or a shock hazard.
 • Make certain alarms are wired to a continuous (non-switched) power line.
 •
 •
 •
 •
 •
 •
 •
 •
 •
 •
NOTE: Use standard UL Listed household wire (as required by local codes) available at all electrical supply 
stores and most hardware stores.
NOTE: AC power should be turned off at this stage.
FUSE OR CIRCUIT BREAKER
Additional
Alarm
RED
BLACK
WHITE
Additional
Alarm
RED
BLACK WHITE
RED
BLACK
WHITE
Kidde Relay Module
SM120X, CO120X
or both 
Optional 
Accessory
First
Alarm
Figure 9-B, Interconnect Wiring Diagram
  Wires on alarm harness:  Connected to: 
  Black:  Hot side of AC line 
  White:  Neutral side of AC line 
  Red:  Interconnect lines (red wires) of other 
    units in the multiple station set-up
Service
 Panel 
 Receptacles  Interconnected alarms 
Wiring practice that has had good results 
in preventing nuisance alarms 
Figure 9-C










