Product Overview
Architectural and Engineering
Specifications
The integrated smoke/CO/strobe alarm shall be Kidde model
P4010ACLEDSCO-2. It shall be powered by a regulated 120VAC, 60 Hz
source with a maximum operating RMS current of 687ma. A sealed 3V
lithium battery provides backup power for the smoke and carbon mon-
oxide alarm only. The temperature operating range shall be between
40˚F (4.4˚C) to 100˚F (37.8˚C) and the humidity operating range shall
be 10 to 95% relative humidity, non-condensing. The unit shall incor-
porate a photoelectric smoke sensor with nominal sensitivity of 2.32 ±
1.35 %/ft OBS. The CO sensor shall be of a fuel cell design and shall
meet the sensitivity requirements of UL 2034.
The integrated smoke/CO/strobe alarm can be installed on any standard
single gang electrical box or a 4” octagon junction box. The electrical
connection (to the alarm) shall be made with a plug-in connector. A
maximum of 24 Kidde devices can be interconnected in a multiple station
arrangement. The interconnect system must not exceed the limit of 18
initiating devices, of which 12 can be smoke alarms. With 18 initiating
devices (smoke, heat, CO, etc), interconnected, it is still possible to inter-
connect 6 standalone strobes (SLED177i) and/or relay modules.
The P4010ACLEDSCO-2 shall include a bright 177 candela strobe light
comprised of 7 LEDs, with a flash rate of one (1) flash per second during
smoke alarm, and 4 flashes every 5 seconds during CO alarm. This unit
shall be interconnected with Kidde smoke alarms, heat detectors and/ or
carbon monoxide alarms. This unit shall automatically synchronize (flash
at the same time) with other P4010ACLEDS-2 and P4010ACLEDSCO-2
strobes that are part of the interconnected system. Synchronization can
take up to 20 seconds when in alarm. Note: The alarms shall not synchro-
nize during a push to test.
The alarm shall include a test feature that will electronically simulate the
presence of smoke and CO, and briefly cause the unit to go into alarm,
when the strobe dome is pressed. This sequence tests the unit’s elec-
tronics to ensure proper operation.
The unit shall also include a Hush® feature that silences the unit for up
to 10 minutes, when the strobe dome is pressed on the initiating alarm,
during a nuisance alarm condition or when the smoke is not too dense.
The red LED on the alarm will flash every 2 seconds while in Hush® and
the unit will automatically reset itself.
In addition to visual flash and LED notifications, this alarm shall have two
methods of audible warnings for danger: a piezoelectric horn that is rated
at 85 decibels at 10 feet and a voice warning that identifies the danger.
If smoke is detected, the horn will sound three (3) long beeps in time
with red LED flashes, followed by “Fire!”. This pattern is repeated until
the smoke is eliminated. The strobe will flash once per second. In the
event of a CO incident, the strobe horn will sound four (4) short beeps
120V AC 3-in-1 LED Strobe and 10-Year Combo
Smoke / CO Alarm. Meets ADA Requirements for the Hearing Impaired
Model Number P4010ACLEDSCO-2
Installation of Smoke Alarm
The alarm should be installed to comply with all local codes hav-
ing jurisdiction in your area, Article 760 of the National Electric
Code, and NFPA 72. Make certain all alarms are wired to a single,
continuous (non-switched) power line, which is not protected by
a ground fault interrupter. A maximum of 1000 ft. of wire can be
used in the interconnect system. Use standard UL listed house-
hold wire as required by code. Wiring shall be in accordance with
articles 210 and 300.3B of the US national electrical code ANSI/
NFPA 70, NFPA 72.
Technical Specifications
Model: P4010ACLEDSCO-2
Power Source: 120VAC (60 Hz, 53ma - 687ma max)
Sensor: Smoke: Photoelectric CO: Electrochemical
Audible Alarm 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10 to 95% relative humidity, non-condensing
Size: 5.9” in diameter x 1.91” depth
Weight: .6 lb
Interconnects: Up to 24 Kidde devices
Warranty: 10 year limited warranty
P/N: KL-P4010ACLEDSCO-2 sheet rev. 06-2018
Distributed by:
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Ordering Information
Ordering Pack Pack Dimensions Cartons/
Number UPC I2F5 Config. Quantity (w x d x h inches) Weight Pallet
21028057 0-47871-28057-5 100-47871-28057-2 Single 3 10.71 x 6.34 x 6.06 3.00 lb 150
Not for sale by individual unit
in time with red LED flashes, followed by “Warning! Carbon
Monoxide!”, repeating every 5 seconds. The strobe will flash 4
times every 5 seconds. This continues until the initiating CO or
combo smoke/CO unit is reset or the CO is eliminated.
The unit shall at a minimum meet the requirements of UL217,
UL2034, UL1971, NFPA 72, The State of California Fire Marshall,
NFPA 101 (One and two family dwellings), Federal Housing
Authority (FHA), Housing and Urban Development (HUD), and
American’s with Disabilities Act (ADA). The alarm shall by listed
by Underwriters Laboratories and include a 10-year manufac-
turer’s limited warranty.