SDS
SAFETY DATA SHEET 
Kidde 90 Multi-Purpose ABC Dry Chemical 
(Fire Extinguishing Agent,  Pressurized and 
Non-pressurized) 
Revision Date: April 10, 2015    Page 4 of 10 
6. 
ACCIDENTAL RELEASE MEASURES 
Personal precautions, protective equipment and emergency procedures 
Wear appropriate protective clothing. Prevent skin and eye contact. Remove leaking container to a safe 
place. Ventilate the area. 
Environmental Precautions 
Prevent large quantities of the material from entering drains or watercourses. 
Methods and materials for containment and cleaning up 
Sweep up or vacuum and transfer into suitable containers for recovery or disposal. 
7. 
HANDLING AND STORAGE 
Precautions for safe handling 
Wear appropriate protective clothing. Prevent skin and eye contact. 
Conditions for safe storage 
Pressurized containers should be properly stored and secured to prevent falling or being knocked over. 
Do not drag, slide or roll pressurized containers. Do not drop pressurized containers or permit them to 
strike against each other. Never apply flame or localized heat directly to any part of the pressurized or 
plastic container. Store pressurized and plastic containers away from high heat sources. Storage area 
should be: - cool - dry - well ventilated - under cover - out of direct sunlight 
8. 
EXPOSURE CONTROLS/PERSONAL PROTECTION 
Control parameters 
Exposure limits are listed below, if they exist. 
Mica 
ACGIH TLV: 3 mg/m
3
 TWA, measured as respirable fraction of the aerosol.  
OSHA PEL: 20 mppcf, <1% crystalline silica 
Clay as Kaolin, Respirable Fraction 
ACGIH TLV: 2 mg/m
3
 TWA 
OSHA PEL: 15 mg/m
3
 TWA, total dust 
 5 mg/m
3
 TWA, respirable fraction 
Nuisance Dust Limit 
OSHA PEL: 50 mppcf or 15 mg/m
3
 TWA, total dust 
 15 mppcf or 5 mg/m
3
 TWA, respirable fraction 
Appropriate engineering controls 
Use  with  adequate  ventilation.  If  this  product  is  used  in  a  pressurized  system,  there  should  be  local 
procedures for the selection, training, inspection and maintenance of this equipment. When used in large 
volumes, use local exhaust ventilation.  
Individual protection measures 
Respiratory Protection 
Not  normally  required.  Use  dust  mask  where  dustiness  is  prevalent,  or  TLV  is  exceeded.  In  oxygen 
deficient  atmospheres,  use a  self  contained breathing  apparatus, as  an  air  purifying respirator will not 
provide protection. 