Product Overview
Plug-In Carbon Monoxide Alarm
AC Powered with Battery Backup
and Digital Display
Part Number 900-0278
Model KN-COP-DP-B
Architectural and Engineering
Specifications
The carbon monoxide alarm shall be Kidde model number KN-
COP-DP-B (Part Number 900-0278) or approved equal. It shall
be powered by a 120VAC, 60 Hz source along with 2 AA alkaline
battery backup. The temperature rating shall be between 40°F
and 100°F (4°C and 38°C) and the humidity operating range shall
be 10% - 95% relative humidity, non-condensing.
The CO sensor shall be of a fuel cell design and shall meet the sen-
sitivity requirements of Underwriters Laboratories UL2034 Single
and Multiple Station Carbon Monoxide Alarms. The unit shall pro-
vide an accuracy of +/- 30% when reading concentration levels.
The alarm shall include an integral plug that can be installed in
any outlet following the UL/NFPA/Manufacturer’s recommended
guidelines. The AC blades remain vertical independent of whether
the electrical socket is mounted vertically or horizontally. The unit
shall incorporate a digital display that meets the sensitivity require-
ments of UL2034. The display will identify the levels of CO in parts
per million (ppm) once that level reaches 30ppm. The display will
automatically dim in low light conditions, and will turn off when
AC power is removed unless more than 100ppm is detected or in
alarm mode.
The alarm shall include a test/reset button. If pressed and released
during normal operation, it shall electronically simulate the pres-
ence of CO and cause the unit to go into alarm. This sequence
tests the unit’s electronics to ensure proper operation. If pressed
during alarm mode, the unit will be silenced and will begin moni-
toring CO levels again.
In accordance with UL2034, the CO sensor will not alarm to levels
of CO below 30 ppm and will alarm in the following time range
when exposed to the corresponding levels of CO.
70 ppm CO concentration 60 – 240 minutes
150 ppm CO concentration 10 – 50 minutes
400 ppm CO concentration 4 – 15 minutes
The alarm shall include a piezoelectric horn that is rated at 85
decibels at 10 feet. When the unit detects carbon monoxide, the
alarm pattern will be four (4) short beeps – followed by five (5)
seconds of silence – followed by four (4) short beeps. A number
reading will appear on the digital display identifying the measured
CO concentration (in ppm).
Technical Specifications
Part Number: 900-0278
Model: KN-COP-DP-B
Power Source: 120VAC, 60 Hz, 90mA max
2- AA battery back-up
Sensor: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4˚C) to 100˚F (38˚C)
Humidity Range: 10%-95% relative humidity (RH),
Non-condensing
Size: 3.0”x 5.6” x 1.5”
Weight: .62 lbs.
Interconnects: No
Warranty: 10 year limited
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
KL-900-0278 sheet rev. 08-2015
Distributed by:
See user guide for additional important information.
!
WARNING: This product is intended for use in ordinary
indoor locations of family living units. It is not designed to measure
compliance with Occupational Safety and Health Administration
(OSHA) commercial or industrial standards.
This device is designed to protect individuals from acute effects of
Carbon Monoxide exposure. It will not fully safeguard individu-
als with specic medical conditions. If in doubt, consult a medical
practitioner. Individuals with medical problems may consider using
warning devices which provide audible and visual signals for carbon
monoxide concentrations under 30 ppm.
Industry experts recommend a CO alarm be installed on each level
of the home--ideally on any level with fuel burning appliances and
outside of sleeping areas.– see User Guide for further information.
Ordering Information
Ordering
No: UPC I 2 of 5
Pack
Cong.
Pack
Qty
Dimensions
(w” x d” x h”)
Weight
(lbs.)
Cartons/
Pallet
21026344 0-47871-26344-8 100-47871-26344-5 Clam 4 11.25 x 7.94 x 11.5 3.5 60