Specification
Architectural and Engineering
Specifications
The smoke alarm shall be Kidde unit 0910/0910CA or approved 
equal. It shall be powered by a non-replaceable lithium battery with a 
10-year life. The lithium battery shall be sealed in the unit to prevent 
removal and/or tampering. The unit shall incorporate an ionization 
sensor with nominal sensitivity of 0.99%/ft (.87%/ft for unit 0910CA). 
The temperature operating range shall be between 40°F and 100°F 
(4°C and 38°C) and the humidity operating range shall be 5% - 95% 
relative humidity.
The smoke alarm can be installed on the surface of any wall or ceil-
ing following the UL/Manufacturer’s approved placement guidelines. 
The alarm shall incorporate an automatic activation feature that will 
activate the unit as soon as it is attached to the mounting bracket, no 
other steps are involved. The alarm shall provide optional tamper resis-
tance that locks the unit to the mounting bracket and deters removal 
of the unit from the wall or ceiling.
The alarm shall include a test button that will simulate a fire condition 
and cause the unit to go into alarm. This sequence tests the unit’s 
electronics to ensure proper operation.
The unit shall include a piezoelectric horn that is rated at 85 decibels 
at 10 feet. The unit shall include the Smart Hush
TM
 feature that silences 
the unit for approximately 7 minutes if a nuisance condition occurs. 
The red LED will illuminate for 1.5 seconds every 8 seconds and will 
automatically reset itself. If the alarm is in the Hush mode and the 
condition that triggered the alarm persists, the alarm shall sound again 
to signal potential danger despite its presence in Hush Mode.The unit 
shall incorporate one red LED to indicate the alarm’s current status 
and mode of operation. The LED will indicate one of four modes:
Standby Mode:  LED will flash every 40-45 seconds to indicate  
    the unit is operating correctly
Alarm Mode:  LED will flash every 1.5 seconds to indicate the 
    unit is alarming and will be accompanied by the 
    horn sounding
Hush Mode:  LED will illuminate for 1.5 seconds every 8  
    seconds to indicate the unit is temporarily silenced
Memory Set Mode:  If Alarm Memory has been set, the LED will 
    flash rapidly when the test button is pressed.
Sealed Battery Unit
Smoke Alarm with Hush
TM
Model 0910
Part Number 900-0136
Technical Specifications
Model:  0910
UPC Number:  0-47871-90136-4
Power Source:  Three, 3V Lithium batteries
Sensor:  Ionization
Audio Alarm:  85dB at 10ft
Temperature Range:  40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range:  5%-95% relative humidity (RH)
Size:  5.6” in diameter x 1.55” depth
Weight:  1.5lbs
Interconnects:  No
LED:  Four modes of operation
Warranty:  10 year limited
  The unit shall include an End of Life Alert which is indicates the 
alarm needs to be replaced. The unit will “chirp” once every 30 
seconds to notify the user. The unit shall have a deactivation switch 
to disable it and make it safe for disposal. The unit shall at a mini-
mum meet the requirements of UL217, NFPA72, (chapter 11 2002 
edition) The State of California Fire Marshall, NFPA101 (One and 
two family dwellings) Federal Housing Authority (FHA), Housing 
and Urban Development (HUD).
Ordering Information
Clamshell UPC:  0 47871 90136 4
Part      Dimensions    Case/  Layers/  Skid
Number I2of5 PackQuantity (wxdxhinches) Weight Skid Skid Weight
900-0136 N/A  N/A  Individual  7.25 x 1.75 x 11  1 lbs  N/A  -----  N/A
900-0136-003  100 47871 90136-1  PDQ (3 units)  7.75 x 6 x 11.75  3 lbs  108  -----  972 lbs
900-0136-020  200 47871 90136-8  Master Pack (20 units)  16 x 24 x 12  20 lbs  12  -----  240 lbs
21007387  400 47871 90136-2  4pc Tray and Lid  7.75 x 9.25 x 11.75  4 lbs  75    300 lbs
5.6" 1.55"
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-0910 sheet    rev. 01-2009