Cut Sheet
10-Year Sealed Battery Powered Combo
Smoke/CO Alarm with Wire-Free Interconnect
Model P4010ACSCO-W
Architectural and Engineering
Specifications
The smoke and carbon monoxide alarm model shall be P4010ACSCO-W or
approved equal and is powered by a 120VAC, 60Hz source along with
lithium battery backup. The lithium batteries shall be sealed in the unit to
prevent removal and/or tampering. The unit shall incorporate a
photoelectric sensor.
The smoke alarm can be installed on any standard single gang electrical
box, up to a 4”octagon junction box, following the UL/Manufacturer’s
approved placement guidelines. The electrical connection (to the alarm)
shall be made with a plug-in connector. The alarm shall incorporate an
activation switch that can be engaged with the included tool or
screwdriver to power on the alarm at startup, and deactivate the alarm at
end of alarm life.
The P4010ACSCO-W shall include a test button that will simulate fire and
carbon monoxide conditions and cause the unit to go into alarm. This
sequence tests the unit’s electronics to ensure proper operation. A
maximum of 24 Kidde devices can be interconnected in a multiple station
arrangement. The interconnect system must not exceed the NFPA (National
Fire Protection Association) limit of 18 initiating devices, of which 12 can
be smoke alarms.
The unit shall have audible methods for warning of smoke or fire danger: a
piezoelectric horn, rated at 85 decibels at 10 feet, and a voice warning. In
a smoke incident, the horn will sound in the repetitive manner – three long
beeps, a 1.5 second pause, three long beeps, repeating. In between, the
unit will announce a voice warning, “Fire!” For a CO incident, the horn will
sound in the repetitive manner - 4 quick beeps, voice message “Warning!
Carbon Monoxide”, 4 quick beeps. The red LED ring will flash in
conjunction with the alarm sound.
The unit shall incorporate wireless alarm interconnect capability, whereas
when one interconnected unit sounds an alarm, all other compatible
wireless units in the wireless alarm network will alarm. The maximum
distance between wireless interconnect models is greater than 300 feet in
open air. The alarm interconnect shall be supervised, where an audible and
visual indication is given if the alarm loses connection to other units in the
network.
The unit shall at a minimum meet the requirements of UL217, UL 2034,
NFPA 72, The State of California Fire Marshall, NFPA101 (One and two
family dwellings), Federal Housing Authority (FHA), Housing and Urban
Development (HUD). The alarm shall be UL Listed and shall include a 10-year
manufacturer’s limited warranty.
Ordering Information
Technical Specifications
Model: P4010ACSCO-W
Power Source: 120VAC (60Hz 53mA Max
Sealed 3V Battery Backup
Sensor: Smoke: Photoelectric
CO: Electrochemical
Audio Alarm: 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: 10 to 95% non-condensing
relative humidity (RH)
Size: 5.59” in diameter x 1.91” depth
Weight: 0.6 lb
Interconnects: Up to 24 Kidde devices
Warranty: 10 year limited
5.59"
5.10"
1.91"
0.45"
1016 Corporate Park Drive
Mebane, NC 27302
1-800-880-6788
www.Kidde.com
Distributed by:
P/N: KL-P4010ACSCO-W sheet rev. 10-2017
Compatible Intelligent Wire-Free 10-Year Models
10-Year Sealed Battery Operated Alarms
P4010DCS-W: Smoke Alarm with Wire-Free Interconnect
P4010LDCS-W: Smoke Alarm with Wire-Free Interconnect and Emergency Safety Light
P4010DCSCO-W: Combination Smoke and CO Alarm with Wire-Free Interconnect
HARDWIRED Alarms with 10-Year Sealed Battery Backup
P4010ACS-W: Smoke Alarm with Wire-Free Interconnect
P4010LACS-W: Smoke Alarm with Wire-Free Interconnect and Emergency Safety Light
P4010ACSCO-W: Combination Smoke and CO Alarm with Wire-Free Interconnect
Leading authorities recommend that both ionization and photoelectric smoke alarms be installed to help ensure maximum detection of the various types of fires
that can occur within the home. Ionization sensing alarms may detect invisible fire particles (associated with fast flaming fires) sooner than photoelectric alarms.
Photoelectric sensing alarms may detect visible fire particles (associated with slow smoldering fires) sooner than ionization alarms.
Ordering No: UPC I 2 of 5
Pack
Cong.
Pack
Qty
Dimensions
(w” x d” x h”) Weight
Cartons/
Pallet
21027323 0-47871-27323-2 100-47871-27323-9 Single
2
8.25 x 6.25 x 9.5 2.5 136