Cut Sheet

Architectural and Engineering
Specifications
The integrated smoke/strobe alarm shall be Kidde model
P4010ACLEDS-2. It shall be powered by a regulated 120VAC, 60 Hz
source with a maximum operating RMS current of 687ma. A sealed 3V
lithium battery provides backup power for the smoke alarm only. The
temperature operating range shall be between 40˚F (4.4˚C) to 100˚F
(37.8˚C) and the humidity operating range shall be up to 95% relative
humidity, non-condensing. The unit shall incorporate a photoelectric
smoke sensor with nominal sensitivity of 2.32 ± 1.35 %/ft OBS.
The integrated smoke/strobe alarm can be installed on any standard
single gang electrical box or a 4” octagon junction box. The electrical
connection (to the alarm) shall be made with a plug-in connector. A
maximum of 24 Kidde devices can be interconnected in a multiple station
arrangement. The interconnect system must not exceed the limit of 18
initiating devices, of which 12 can be smoke alarms. With 18 initiating
devices (smoke, heat, CO, etc), interconnected, it is still possible to
interconnect 6 standalone strobes (SLED177i) and/or relay modules.
The unit shall incorporate a three-color LED ring, that when illuminated,
specifies the current condition of the alarm. The LED ring is green
when receiving AC power, red when smoke is detected, and amber in
a trouble condition. The ambient light sensor causes the green LED to
stay on continuously during light conditions, or blink every 60 seconds
during dark conditions. The green LED will blink every 60 seconds when
operating on battery backup power.
The P4010ACLEDS-2 shall include a bright 177 candela strobe light
comprised of 7 LEDs, with a flash rate of one (1) flash per second
during smoke alarm. This unit shall be interconnected with Kidde
smoke alarms, heat detectors and/ or carbon monoxide alarms. This
unit shall automatically synchronize (flash at the same time) with other
P4010ACLEDS-2 and P4010ACLEDSCO-2 strobes that are part of the
interconnected system. Synchronization can take up to 20 seconds when
in alarm. Note: The alarms shall not synchronize during a push to test.
The alarm shall include a test feature that will electronically simulate the
presence of smoke and briefly cause the unit to go into alarm, when
the strobe dome is pressed. This sequence tests the unit’s electronics to
ensure proper operation.
The unit shall also include a Hush® feature that silences the unit for up
to 10 minutes, when the strobe dome is pressed on the initiating alarm,
during a nuisance alarm condition or when the smoke is not too dense.
The red LED on the alarm will flash every 2 seconds while in Hush® and
the unit will automatically reset itself.
In addition to visual flash and LED notifications, this alarm shall have two
methods of audible warnings for danger: a piezoelectric horn that is rated
at 85 decibels at 10 feet and a voice warning that identifies the danger.
120V AC 2-in-1 LED Strobe and 10-Year Smoke Alarm.
Meets ADA Requirements for the Hearing Impaired
Model Number P4010ACLEDS-2
Installation of Smoke Alarm
The smoke alarm should be installed to comply with all local
codes having jurisdiction in your area, Article 760 of the National
Electric Code, and NFPA 72. Make certain all alarms are wired
to a single, continuous (non-switched) power line, which is not
protected by a ground fault interrupter. A maximum of 1000 ft.
of wire can be used in the interconnect system. Use standard
UL listed household wire as required by code. Wiring shall be
in accordance with articles 210 and 300.3B of the US national
electrical code ANSI/NFPA 70, NFPA-72.
Technical Specifications
Model: P4010ACLEDS-2
Power Source: 120VAC (60 Hz, 53ma - 687ma max)
Sensor: Photoelectric
Audible Alarm 85dB at 10ft
Temperature Range: 40˚F (4.4˚C) to 100˚F (37.8˚C)
Humidity Range: Up to 95% relative humidity, non-condensing
Size: 5.9” in diameter x 1.91” depth
Weight: .6 lb
Interconnects: Up to 24 Kidde devices
Warranty: 10 year limited warranty
P/N: KL-P4010ACLEDS-2 sheet rev. 06-2018
Distributed by:
1016 Corporate Park Drive
Mebane NC 27302
1-800-880-6788
www.Kidde.com
Ordering Information
Ordering Pack Pack Dimensions Cartons/
Number UPC I2F5 Config. Quantity (w x d x h inches) Weight Pallet
21026872 0-47871-26872-6 100-47871-26872-3 Single 3 10.71 x 6.34 x 6.06 3.00 lb 150
Not for sale by individual unit
If smoke is detected, the horn will sound three (3) long beeps
in time with red LED flashes, followed by “Fire!”. This pattern is
repeated until the smoke is eliminated. The strobe will flash once
per second. When interconnected with a carbon monoxide alarm
or combination smoke/CO alarm, in the event of a CO incident
detected by the CO or combo smoke/CO alarm, the strobe horn
will sound four (4) short beeps in time with red LED flashes,
followed by “Warning! Carbon Monoxide!”, repeating every
5 seconds. The strobe will flash 4 times every 5 seconds. This
continues until the initiating CO or combo smoke/CO unit is reset
or the CO is eliminated.
Note: This alarm DOES NOT detect carbon monoxide.
The unit shall at a minimum meet the requirements of UL217,
UL1971, NFPA 72, The State of California Fire Marshall, NFPA 101
(One and two family dwellings), Federal Housing Authority (FHA),
Housing and Urban Development (HUD), and American’s with
Disabilities Act (ADA). The alarm shall by listed by Underwriters
Laboratories and include a 10-year manufacturer’s limited
warranty.