User's Manual
TM0081 Page 27 of 51 Issue 1.01
9.5 TEST MENU
The Test menu Table 9 provides the user dependent upon Access level with the following options.
Sub-Menu 1 Access
Level 2
Access
Level 3
Function
Panel Test
""
Press enter (↵) button to initiate a panel LED, LCD display & Buzzer test and MCP
software version installed.
Device Test -
"
Enter the device parameters to be tested and press enter (↵) button to confirm.
Automatic detectors pulse the base alarm LED during the test.
Output group test -
"
Enter the output group number to be operated and press enter (↵) button. WARNING,
ensure that output groups programmed to operate release units are isolated locally.
Press silence alarms button to de-activate the output group and reset to select a new
group to be tested or cancel to return to menus.
Alarm simulation -
"
Enter the device parameters to be tested and press enter (↵) button. WARNING,
Output Groups will operate, ensure that groups programmed to operate release units
are isolated locally. Press silence buzzer, silence alarms & reset buttons to return to
status normal.
Key test -
"
Press enter (↵) button to initiate test and operate fascia key buttons as required. To
exit test option, press the cancel (←) button.
Test mode -
"
Select activate & press enter (↵) button. Enter zone number to be tested & press enter
(↵) button. To quit zone test mode, select de-activate & press enter (↵) button.
Table 9: Test Menu