User's Manual

TM0081 Page 27 of 51 Issue 1.01
9.5 TEST MENU
The Test menu Table 9 provides the user dependent upon Access level with the following options.
Sub-Menu 1 Access
Level 2
Access
Level 3
Function
Panel Test
""
Press enter () button to initiate a panel LED, LCD display & Buzzer test and MCP
software version installed.
Device Test -
"
Enter the device parameters to be tested and press enter () button to confirm.
Automatic detectors pulse the base alarm LED during the test.
Output group test -
"
Enter the output group number to be operated and press enter () button. WARNING,
ensure that output groups programmed to operate release units are isolated locally.
Press silence alarms button to de-activate the output group and reset to select a new
group to be tested or cancel to return to menus.
Alarm simulation -
"
Enter the device parameters to be tested and press enter () button. WARNING,
Output Groups will operate, ensure that groups programmed to operate release units
are isolated locally. Press silence buzzer, silence alarms & reset buttons to return to
status normal.
Key test -
"
Press enter () button to initiate test and operate fascia key buttons as required. To
exit test option, press the cancel () button.
Test mode -
"
Select activate & press enter () button. Enter zone number to be tested & press enter
() button. To quit zone test mode, select de-activate & press enter () button.
Table 9: Test Menu