User's Manual

TM0081 Page 26 of 51 Issue 1.01
9.4 SET MENU
The Set menu Table 8 provides the user dependent upon Access level with the following options.
SET – Menu Functions
Sub-Menu 1 Sub- Menu 2 Access
Level 2
Access
Level 3
Function
Time & Date
""
Enter revised Time, select AM or PM, 12 hr or 24 hr format
and enter Day/Month/Year and press enter () button to
confirm.
Printer Status Printer type
""
Confirms the type of printer currently installed. Standard Dot
Matrix or Thermal type. Note: Vega LT uses Thermal only.
Printer status
""
Confirms the current status of the printer – enabled or
disabled.
Select type
""
Select type of printer installed – Standard or Thermal and
press enter () button to confirm selection.
Select status
""
Controls the operation of the printer – Select Enable or
Disable and press enter () button to confirm. Note: When
the printer is installed correctly and disabled status is set,
the printer will automatically print priority 0 & 1 events.
Activate day
mode
Day mode status
""
Confirms the current day mode status – active or inactive.
Select status
""
Controls the operation for day mode – Select Activate or
Deactivate and press enter () button to confirm.
Standard features -
"
Custom features -
"
Refer to Programming section of this manual.
Clear memory Zone info -
"
To clear Fire Zone info - press enter () button to confirm.
Plant info -
"
To clear Plant Zone info - press enter () button to confirm.
Group info -
"
To clear Output Group info - press enter () button to
confirm.
Device info -
"
To clear loop device info - press enter () button to confirm.
BLC outputs -
"
To clear MBLC info - press enter () button to confirm.
Activations -
"
To clear Activations info - press enter () button to confirm.
Motherboard info -
"
N/A
User passwords Change level 2 -
"
Enter new level 2 pass code ####, Re-enter new level 2
code #### and press enter () button to confirm.
Change level 3 -
"
Enter new level 3 new pass code ####, Re-enter new level
3 pass code #### and press enter () button to confirm.
Loop config Accept logon
count
-
"
An option is provided to view new devices added or
removed from the specified detection loop. Select ‘Yes’ and
press enter () button to confirm devices accepted.
Accept config
count
-
"
Download configuration device faults. Devices that do not
match the VIPER upload download site file are flagged as a
config fault and are listed.
Autolearn -
"
Enables the user to automatically re learn devices for the
specified loop number.
Table 8: Set Menu