User's Manual

TM0081 Page 24 of 51 Issue 1.01
9.2 ISOLATE \ DE-ISOLATE MENU
The isolate menu list Table 6 provides the user dependent upon Access level with the following options.
ISOLATE – Menu Functions
Sub-Menu 1 Sub- Menu 2 Access
Level 2
Access
Level 3
Function
Zones
""
Enter fire zone number to be isolated and confirm isolation
using enter ()
button from list of zones presented. To de-
isolate, select isolated (flashing) zone from list and press
enter () button to de-isolate.
Loop devices Single device
""
Enter loop & device parameters and confirm isolation using
enter () button from the list of devices presented. To de-
isolate, select isolated (flashing) device from the list and
confirm de-isolation using enter () button.
Isolate range
""
Enter range of device parameters and confirm isolation
using enter () button.
De-Isolate range
""
Enter range of device parameters and confirm de-isolation
using enter () button.
Output groups Single groups
""
Enter output group number and confirm isolation using enter
() button from the list of output groups presented. To de-
isolate the output group, select isolated (flashing) group
from the list and confirm de-isolation using enter () button.
Isolate Range
Enter range of output group numbers and confirm isolation
using enter () button.
De-Isolate Range
""
Enter range of device numbers and confirm de-isolation
using enter () button.
Panel functions BLC outputs
""
Select from the list the MBLC output to be isolated and
confirm isolation using enter () button. To de-isolate, select
(flashing) output to be de-isolated and press enter ()
button.
Motherboard - - N\A
Plant
""
Enter plant zone number to be isolated and confirm isolation
using enter ()
button from list of zones presented. To de-
isolate, select isolated (flashing) zone from list and press
enter () button to de-isolate.
Local Buzzer -
"
Table 6: Isolation \ De-isolation Menu