To review additional zone fault information, press enter (↵) button.
!
The display updates providing additional zone fault specific information. Refer to Figure 27.
Figure 27: Zone Fault Condition – Zone & Device information
6.4.3 Group Fault Conditions
Group faults relate to detection loop output modules such as sounder circuit controllers, loop powered sounders
and the output channel of the input \ output modules. These types of devices are assigned during
commissioning to output group numbers, which are then programmed into cause & effect strategies. Output
groups then operate during a zone priority 1 fire condition ringing sounders, bells and operating shutdown etc.
Note: Input devices (Smokes, Break Glass, Input modules) are assigned to Zones while output devices
(Sounder modules, Output modules & Loop sounders) are assigned to output groups.
If a group fault occurs, generally as a result of a faulty loop device:
!
The yellow COMMON FAULT light flashes
!
An audible buzzer on the panel sounds intermittently
!
The event printer prints out the full fault alarm details (when installed and fully enabled)
!
The display updates providing the user with the alarm header text, total number of alarms within
the fault priority queue, group fault information and total number of group faults present. Refer
to Figure 28.
Figure 28: Group Fault Condition
!
To review additional zone fault information, press enter (↵) button.
!
The display updates providing additional group fault specific information. Refer to Figure 29.
Figure 29: Group Fault Condition – Group & device Information