User's Manual
TM0081 Page 19 of 51 Issue 1.01
Figure 19: Fire Condition – Zone information
!
To view additional device information, press enter (↵) button.
!
The display updates providing additional device specific information, device loop, zone and address
numbers, total number of active devices within the zone, device type and 24 characters of device
specific location text. Refer to Figure 20.
Figure 20: Fire Condition – Zone & Device Information
Should additional fire conditions be detected within the same zone, then the total fire counter will increase and
the event printer prints out the full alarm details (when installed). The total number of active zones counter will
remain as one. Refer to Figure 21. The scroll button is used to view the additional device within the zone in
alarm.
Figure 21: Multiple Fire Conditions – Same Zone
Should a second zone fire condition be detected,
!
The relevant red zone alarm light flashes
!
The red ALARM light flashes
!
The alarm sounders circuits are activated (unless already active or delays are programmed)
!
An audible buzzer on the panel sounds
!
The event printer prints out the full alarm details (when installed)
!
The display updates providing the user with the alarm header text, total number of alarms, zone
number and 24 character zone location text. Refer to Figure 22.
Figure 22: Multiple Fire Conditions – Different Zones
Note, The highlighted zone location text indicates to the user which zone the device specific information relates
to. Using the navigation arrow keys in conjunction with the scroll button, the user can browse through the
various alarms present on the display.