User's Manual

P/N 81-CO2MAN-001 v September 2013
Installation
THIS SEQUENCE FOR CYLINDER INSTALLATION MUST BE FOLLOWED AT ALL TIMES:
1. Position cylinder(s) in designed location and secure with cylinder bracket(s).
2. Remove safety (shipping) cap and actuation port protection cap.
3. Attach flex loops or swivel adapter to discharge heads. Connect assembly to system piping. Then
attach assembly to cylinders.
4. Verify control head(s) are in the set position.
5. Install control head(s) on cylinder(s).
Removal From Service
1. Remove control head(s) from cylinder(s).
2. Remove discharge head from each cylinder valve.
3. Attach safety (shipping) protection cap and actuation port protection cap to each cylinder.
4. Remove cylinder from bracketing and properly secure to hand truck. Properly secure each cylinder for
transport. Repeat for remaining cylinders.
WARNING
Flex hoses/swivel adapters must always be connected to the system piping and
to the discharge heads before attaching the discharge heads to the cylinder
valves in order to prevent injury in the event of inadvertent carbon dioxide
discharge.
WARNING
Control heads must be in the set position before attaching to the cylinder
actuation port in order to prevent accidental discharge.
WARNING
Do not remove the cylinder from the bracketing if the safety and protection caps
are missing. Obtain a new safety (shipping) cap from a local gas supplier.
Obtain a new actuation port protection cap from Kidde Fire Systems.