Component Descriptions
P/N 81-CO2MAN-001 2-27 September 2013
2-3.4 Electric Control Heads
2-3.4.1 ELECTRIC CONTROL HEADS
The electric control heads (Figure 2-31 and Figure 2-32) provide for electric and local manual
actuation of the CO
2
cylinder valve, or directional (stop) valves. The control head is operated
electrically by a suppression control panel and is equipped with a lever for local manual
operation.
The electric control head contains a microswitch whose contacts are used to break the electrical
circuit to the solenoid when the head is actuated. This reduces the overall power consumption
of the fire suppression system. The actuating pin latches in the released position and must be
mechanically reset.
A suitable suppression control panel, specifically listed and/or approved for use with the
following control heads, shall be provided for supervision of the releasing circuits per NFPA
requirements. In addition, a 24 hour back-up power source shall be provided per NFPA
requirements. Electrical data is contained in Table 2-8.
Figure 2-31. Electric Control Head
ELECTRIC
CONTROL HEAD
VOLTS
AMPS
PART NO.
SET RELEASED
MADE IN U. S. A.
TO RESET
USE SCREWDRIVER
KIDDE-FENWAL, INC.
400 MAIN STREET
ASHLAND, MA 01721
SEAL WIRE
INDICATOR AND
RESET STEM
6-3/16 in.
(157 mm)
CONNECTION FOR FLEXIBLE
ELECTRICAL CONDUIT
3/4 in. NPT FEMALE
LOCKING PIN
LOCAL MANUAL
RELEASE LEVER
SWIVEL NUT
1-1/2 in. (38 mm) HEX
1-1/4 in. - 18 NF-3 THREAD
4 in.
(102 mm)