User's Manual
Component Descriptions
September 2013 2-24 P/N 81-CO2MAN-001
Figure 2-26. Tee Pulley
2-3.3.5 ADAPTER
The adapter, Part No. WK-843837-000 (Figure 2-27), is used to connect 1/2-inch EMT to
components with 3/8-inch NPS outlets such as the cable operated control head and the dual
pull equalizer. This adapter has a 1/2-inch female EMT connector on one end and a 3/8-inch
NPS male connector on the other end.
Figure 2-27. EMT Adapter
2-3.3.6 CABLE HOUSING
A cable housing (Figure 2-28) is required when the suppression system consists of three or
more cylinders and utilizes two cable-operated control heads. The cable housing protects the
interconnecting cable between the two cable-operated control heads and secures the two
heads in a fixed position. The length of the cable housing (see Table 2-6) is determined by the
size of the cylinders used in the suppression system.
Kidde
1/16 in. CABLE
PULLEYS
CABLE CLAMP - SUPPLIED
WITH TEE PULLEY
SINGLE 1/16 in. CABLE
1/2 in. EMT
4-5/16 in.
(110 mm)
4-1/2 in.
(114 mm)
(3) 1/2 in. EMT CONNECTIONS
COMPRESSION TYPE
COVER HELD ON BY
(4) NO. 10 SCREWS
THRU HOLES SHOWN
1/2 in. EMT CONNECTION
COMPRESSION TYPE
3/8 in. NPS MALE
1-1/2 in.
(39 mm)