User's Manual
P/N 81-CO2MAN-001 C-1 September 2013
APPENDIX C
EUROPEAN EQUIPMENT
C-1 INTRODUCTION
Kidde Fire Systems CO
2
equipment sold into the European Union must comply with Pressure
Equipment Directive (PED) 97/23/EC and Transportable Pressure Equipment Directive (TPED)
1999/36/EC. Refer to Table C-1 for a list of equipment.
Equipment, such as discharge heads, flex hoses, check valves, etc., that will be exposed to
pressure during a discharge shall be PED approved. PED approval is indicated by the CE mark
affixed to these components.
Equipment, such as cylinders and discharge valves, that retain pressure while during transport,
shall be TPED approved. TPED approval is indicated by the PI mark affixed to these components.
Table C-1. TPED and PED Approved Equipment for European Community Only*
Part No. Description
81-870287-002 75 lb. CO
2
Cylinder and Valve Assembly- "Pi" marked and CE approved
81-870269-002 100 lb. CO
2
Cylinder and Valve Assembly - "Pi" marked and CE approved
WK-981372-002 1/2-inch I-Valve - TPED Approved
WK-840253-002 5/8-inch I-Valve - TPED Approved
81-897494-001 Electric/Cable Control Head, 24 VDC ATEX/CE (NOT UL/FM)
81-100000-001 Explosion Proof Electric Control Head, Stackable, 24 VDC, ATEX Approved
* Component Equipment Only