User's Manual
P/N 81-CO2MAN-001 B-7 September 2013
B-6 PNEUMATIC MAIN-TO-RESERVE VALVE
The pneumatic main-to-reserve transfer valve, Part No. 871364 (Figure B-5), is installed in
pneumatically-actuated systems having a connected main and reserve supply of carbon
dioxide, and is used to direct the pneumatic actuation signal to either the main or the reserve
pilot cylinders.
The valve contains an inlet port which is connected to two outlet ports. A toggle switch controls
a lever that transfers the pneumatic signal to one of the two outlet ports while blocking its
passage to the other. The toggle switch is normally placed in the "main" position. In the event
that the main suppression system discharges, the switch is placed in the "reserve" position to
provide uninterrupted fire protection while the main system is being recharged.
Figure B-5. Pneumatic Main-to-Reserve Valve
CAUTION
Never move the main-to-reserve transfer valve to the "reserve" position,
following a main suppression system actuation, unless the activating
detector(s) has/have cooled down.
RESERVE
MAIN
DO NOT FORCE BEYOND STOP POSITION
COVER OPEN
U
L
PNEUMATIC SELECT OR VALVE
TO SHIFT FR OM MAIN
TO RESER VE CYLINDERS
1.LIFT COVER
2.MOVE LEVER T O RIGHT
KIDDE-FENWAL, INC.
400 MAIN STREET,ASHLAND, MA 01721
TEL: (508)881-2000 FAX: (508)881-8920
PART NO. 871364
(162mm)
COVER CLOSED
6-3/4 in.
(171 mm)
7 in.
(178 mm)
NAMEPLATE
RING - PULL TO
OPEN COVER
ENCLOSURE
6 MOUNTING HOLES
TOGGLE LEVER