User's Manual

Installation
P/N 81-CO2MAN-001 4-43 September 2013
4-4.11.2 NITROGEN PILOT CYLINDER INSTALLATION, 1040 CU. IN. AND 2300 CU. IN., P/NS
90-101040-000 AND 90-102300-100
The nitrogen pilot cylinders must be located as close to the hazard area as possible. The
storage location must be protected from the elements and maintained at a temperature
between 32°F (0°C) and 130°F (54°C). External heating and/or cooling may be required
to maintain this temperature range. Cylinders should be raised at least 2 in. (50 mm)
from the deck using a suitable bracket or blocks if the area is regularly washed down or
is subject to environmental wetting.
Single cylinders should be installed using two straps, P/N WK-270014-000, installed at
the heights shown in Figure 4-33. See Table 4-5 for strap dimensions. Where two
cylinders are installed, two double straps, P/N WK-241219-000 can be used. Install at
the same heights defined for single cylinder straps.
Figure 4-33. Typical 1040 and 2300 cu. in. Pilot (Driver) Cylinder Strap Installation (P/N 90-101040-000
and 90-102300-100)
WARNING
Nitrogen cylinders must not be moved unless the discharge and control heads
have been removed and the protection caps are installed. Failure to follow these
instructions could result in inadvertent discharge, serious bodily injury, death
or property damage.
Table 4-5. 1040 and 2300 cu. in. Nitrogen Pilot (Driver) Cylinder Strap Installation
Part Number Description
ABC
in. mm in. mm in. mm
90-101040-000 1040 cu. in. 21 to 22 533 to 559 6 to 8 152 to 203 10.4 263
90-102300-100 2300 cu. in. 42 to 44 1067 to 1118 12 to 14 305 to 356 10.4 263
A
C
B