User's Manual
Installation
P/N 81-CO2MAN-001 4-21 September 2013
Figure 4-18. Rack Framing - 11 to 20 Cylinders (100 lb. Capacity), Double Row (One Side)
11 - 12 CYL.
15 - 16 CYL.
17 - 18 CYL.
19 - 20 CYL.
NOTES:
THIS FRAMEWORK TO BE PLACED AGAINST A WALL, BUT CAN
BE ALSO BE INSTALLED FREE STANDING.
ALLOW 2 ft. (610 mm) CLEARANCE IN FRONT OF CYLINDERS FOR SERVICE.
ALLOW 2 ft. (610 mm)
AISLE IN FRONT OF CYLINDERS FOR SERVICING.
CHANNEL SUPPORT
WK-207281-000 - FASTEN WITH
(4) 3/8 in. X 1 in. LG. BOLTS
AND NUTS
GUSSET - WK-241211-000
FASTEN TO FLOOR
CYLINDER CHANNEL
(SEE TABLE)
MANIFOLD AND
WEIGHING BAR
BRACKET (SHOWN IN
POSITION FOR 100 LB.
CAP CYLS.) - WK-271568-000
FASTEN WITH 3/8 in. X
1 in. LG. BOLTS AND
NUTS
WEIGHING BAR (SEE TABLE)
FASTEN WITH 3/8in. X
1 in. LG. BOLTS AND
NUTS
CHANNEL SUPPORT
- WK-207281-000 FASTEN WITH
(3) 3/8 in. X 1 in. LG.
BOLTS
SLOT FOR PIPE CLAMP
6 ft. 2 in.
THESE HOLES FOR PNEUMATIC SYSTEM ONLY
HOLES FOR PNEUMATIC SELECTION VALVE
HOLES FOR KNOCKOUT JUNCTION BOX
TABLE
(2) WK-
(2) WK-
243796-000
-000243797
WK- -000
WK- -000
271563
271564
19-20
17-18
15-16
13-14
NO.
CYLS
LENGTH
CYL
CHANNEL
P/N
WEIGH
BAR P/N
7 ft.
8 ft. 8 in.
6 ft. 2 in.
(2) WK-
(2) WK-
-000
-000
243797
243798
(2) WK-271563-000
(4) WK- -000243797
WK- -000
WK- -000
271564
271565
243796-000(2) WK-
(4) WK- -000243798
5 ft. 4 in.
11-12
(2) WK- -000
271565
7 ft. 10 in.
(2) WK- -000
271564
11 5/8 in. CENTERS
100 LB. CAP. CYL.
13-5/16 in
.
16-5/16 in.
32-1/2 in.