4-3.4 Manifold “Y” Fitting
When the carbon dioxide system consists of two (2) cylinders this fitting (P/N 207877) may be
used to connect the Flex Hoses to the pipe network riser.
Refer to Paragraph 4-3.6 for information on Flex Hose installation.
Figure 4-2. Manifold “Y” Fitting
4-3.5 Carbon Dioxide Cylinder Assemblies
The carbon dioxide cylinders must be located as close to the hazard area as possible. The
cylinders must be located in an environment protected from the weather and where ambient
storage temperatures for, (a) local application systems shall not exceed 120°F (49°C) nor be
less than 32°F (0°F); and (b) total flooding systems shall not exceed 130°F (54°C) nor be less
than 0°F (-18°C). External heating or cooling may be required to maintain this temperature
range.
Orient the cylinders according to the approved installation drawings. Mount the cylinders
securely to the structural supports with the straps and/or brackets provided. Elevate the
cylinders at least two inches off the floor if moisture is present. Locate the cylinder straps as
shown in Figure 4-3 and Figure 4-5. For other strap and bracketing arrangements refer to
Figure 4-5 through Figure 4-20.
Reprinted with permission from NFPA 12-2005. Carbon Dioxide Extinguishing Systems, Copyright © 2005, National Fire Prevention Association,
Quincy, MA 02169. This reprinted material is not the complete and official position of the NFPA on the referenced subject, which is represented
only by the standard in its entirety
WARNING
Each cylinder strap and/or bracket must be securely attached to structural
supports to absorb the force generated by cylinder discharge.
207877
3/4 in. NPT FEMALE(DN20)
3/4 in. (DN20) NPT FEMALE
3/4 in. (DN20) NPT FEMALE