User's Manual

Installation
P/N 81-CO2MAN-001 4-3 September 2013
1
Extracted from FSSA Pipe Design handbook, Second Edition, with permission of the publisher,
FSSA.
Additional Pipe Hanger and Support Considerations:
Riser supports shall take into consideration the weight of the entire riser including pipe,
valves and other concentrated loads
Pipe supports shall be located at each change in direction
Pipe supports shall be located as close as possible to concentrated loads
Table 4-1. Maximum Horizontal Pipe Hanger and Support Bracing
1
Pipe Size Distance Between Supports Rod Diameter
1/4 in. (DN06) 7 ft. (2.1 m) 3/8 in.
1/2 in. (DN15) 7 ft. (2.1 m) 3/8 in.
3/4 in. (DN20) 7 ft. (2.1 m) 3/8 in.
1 in. (DN25) 7 ft. (2.1 m) 3/8 in.
1-1/4 in. (DN32) 7 ft. (2.1 m) 3/8 in.
1-1/2 in. (DN40) 9 ft. (2.7 m) 3/8 in.
2 in. (DN50) 10 ft. (3 m) 3/8 in.
2-1/2 in. (DN65) 11 ft. (3.4 m) 1/2 in.
3 in. (DN80) 12 ft. (3.7 m) 1/2 in.
4 in. (DN100) 14 ft. (4.3 m) 5/8 in.
5 in. (DN125) 16 ft. (4.9 m) 5/8 in.
6 in. (DN150) 17 ft. (5.2 m) 3/4 in.
8 in. (DN200) 19 ft. (5.8 m) 3/4 in.