User's Manual

Design
September 2013 3-82 P/N 81-CO2MAN-001
3-16.4.3 MULTIPLE STATIONS
Where simultaneous use of two or more hose lines from a single bank of cylinders is possible,
a quantity of carbon dioxide shall be available to support the maximum number of hoses that
are likely to be used at any one time for at least 1 minute. All supply piping shall be sized for
the simultaneous operation of these hoses.
3-16.4.4 CARBON DIOXIDE SUPPLY
A separate carbon dioxide supply can be provided for hand hose line use, or carbon dioxide can
be piped from a central storage unit supplying several hose lines or from fixed manual or
automatic systems. Where hand hose lines are provided for use on a hazard protected by a
fixed system, separate supplies shall be provided unless sufficient carbon dioxide is provided
to ensure that the fixed protection for the largest single hazard on which the hose lines can be
used will not be jeopardized.
All controls for actuating the system shall be located in the immediate vicinity of the hose reel
or rack. Operation of hand hose line systems depends upon manual actuation and manual
manipulation of the horn and valve assembly. Therefore, speed and simplicity of operation are
essential for successful extinguishment. Refer to Paragraph 3-13 for additional information on
actuation systems.
The use of a Grooved Nut Discharge Head, P/N 81-872442-000, with a Lever Operated Control
Head, P/N WK-870652-000, allows the operator to actuate only one cylinder at a time in a
multiple cylinder bank and to close the cylinder valve without discharging the entire contents
of the cylinder.
3-16.4.5 ACTUATION
All controls for actuating the system shall be located in the immediate vicinity of the hose reel
or rack. Operation of hand hose line systems depends upon manual actuation and manual
manipulation of the horn and valve assembly. Therefore, speed and simplicity of operation are
essential for successful extinguishment. Refer to Paragraph 3-13 fir additional information on
actuation systems.
The use of a Grooved Nut Discharge Head, P/N 81-872442-000, with a Lever Operated Control
Head, P/N WK-870652-000, allows the operator to actuate only one cylinder at a time in a
multiple cylinder bank and to close the cylinder valve without discharging the entire contents
of the cylinder.