User's Manual

Design
P/N 81-CO2MAN-001 3-43 September 2013
From Equation (25):
Where is the Length of the Nozzle Coverage Area.
= 7 2
= 3-1/2 ft.
From Equation (26):
Where is the Actual Nozzle Coverage Area.
= x
= 3 x 3.5
= 10-1/2
ft.
2
From Equation (27):
Where N is the Total Quantity of Nozzles.
= 1 x 2
= 2 nozzles
From Equation (28):
Where is the Total Discharge Rate and is the Discharge Rate of Single Nozzle.
= 4.23 lb./min./
ft.
2
.
= 4.23 x 10.5 x 2
= 89 lb./min
s