User's Manual
Design
September 2013 3-38 P/N 81-CO2MAN-001
3-6.2.2.2 Rate for Coated Surface
The minimum flow rate per coverage area per nozzle for tankside protection of coated surfaces
shall be selected from Table 3-8.
Table 3-8A. Coated Surfaces
1
(US Units)
Area
(ft.
2
)
Min. Rate
(lb./min.-ft.
2
)
Max. Rate
(lb./min.-ft.
2
)
1 2.96 37.2
2 2.96 19.4
3 2.96 13.2
4 2.96 10.2
52.968.4
62.967.2
72.966.3
82.965.7
92.965.2
10 2.96 4.8
11 2.96 4.5
12 2.96 4.2
13 2.96 4.0
14 2.96 3.8
15 3.09 3.6
16 3.19 3.5
16.5 3.39 3.4
1
CO
2
required is approximately 2 lb./ft.
2