User's Manual
TM0110 Page 9 of 22 Issue 1.00
2.4 DISABLEMENTS
The disablement function allows the operator to disable several panel functions.
The ZONE DISABLEMENT function allows the user to enable/disable one or more zone monitoring
circuits. If a zone monitoring circuit is disabled, the panel ignores that zone’s fire, short circuit fault,
open circuit fault or head removed fault conditions. The disabled zone does not affect any of the
other zone monitoring circuits. In the quiescent state, a disabled zone is indicated by the ZONE fault
light on and the GENERAL DISABLE light on.
The ALARM DISABLEMENT function allows the user to enable/disable the panel alarm circuits. This
inhibits the panel fire alarm devices from operation when an alarm condition occurs. It also inhibits
the panel from monitoring for an open or short circuit fault condition. In the quiescent state, the alarm
disablement condition is indicated by the SOUNDER STATUS fault light on and the GENERAL
DISABLE light on.
The FIRE DISABLEMENT function allows the user to enable/disable the panel fire output. This
inhibits the fire outputs from operation when any panel zone fire alarm condition occurs. It also
inhibits the panel from monitoring for a fire output open or short circuit fault condition. In the
quiescent state, the fire output disablement condition is indicated by the FIRE OUTPUT STATUS light
on and the GENERAL DISABLE light on.
2.5 VIEW
The view function allows the user to view the total amount of panel alarms registered.
The Access Level 2 menu structure is summarised in Figure 3:
Figure 3: Access Level 2 Menu Structure
NOTE: Access Level 3 options are detailed in Chapter 3 –
Installation & Commissioning.
MENU
1: USER FUNCTION TIME/DATE *ENTER NEW DATE*
DD/MM/YYYY
VIEW ALARM COUNTER *ALARM COUNTER*
TOTAL ALARMS 0
DISABLEMENTS ZONE DISABLEMENT ZONE 1 ENABLED
ALM DISABLEMENT AUX ALARMS EN
FIRE DISABLEMENT AUX FIRE EN
DAY/NIGHT MODE
2: ENT ENG CODE *ENGINEER CODE*
7134 (DEFAULT)
2
1
SEL
SEL
SEL
SEL
SEL
SEL
SEL
SEL
UP
UP
UP
SEL