User's Manual
TM0110 Page 6 of 22 Issue 1.00
The following controls are available in Access Level 2:
SILENCE / RESOUND
ALARMS
If the panel has a zone fire state, operation of the SILENCE / RESOUND
ALARMS switch silences all alarm devices, ALARM and ZONE fire lights
stop flashing and stay on constantly and the buzzer sounds intermittently. If
a new zone alarm condition occurs, the fire state conditions are re-enabled.
Repeat operations of the switch toggles the panel between re-sounding and
silencing of the external alarms and the panel buzzer.
RESET If the panel has standing faults on the display, operation of the RESET
switch clears these faults. If the panel has any standing alarm conditions,
the SILENCE RESOUND ALARMS switch MUST be operated first to enable
the RESET switch. System reset forces the panel into a quiescent state. If
standing panel alarms or faults remain, after a short delay they will be re-
enabled.
NOTE: After operation of the RESET switch the panel has a delay of
about 5 seconds before any other switch can be activated (except test
lamps).
SILENCE BUZZER If there is an alarm, panel access must be enabled for operation of this
switch. If the panel internal buzzer is sounding, operation of the SILENCE
BUZZER switch silences the panel buzzer. Any new event resounds the
buzzer and operation of the switch is again required to silence it.
SCROLL Operation of the SCROLL switch when more than 2 panel events are active,
updates line 1 of the display with the next event in the queue. Line 1 reverts
back to the first panel event if this switch is not pressed within 10 seconds.
TEST This switch is always active. Operation of the switch makes all display lights
come on and also sounds the panel buzzer continuously.
MENU Operation of the MENU switch allows the user to select panel operator
functions and engineer functions. To enable panel engineer functions the
user must initially enter the 4 digit engineer code (refer to Table 1).
ENTER The ENTER switch is used to accept user and engineer function
configuration changes.
ACCESS The ACCESS switch allows the operator to input the 4 digit code to allow
panel access. When the panel is accessed the PANEL ACCESS light
comes on, all key switches are enabled and operator access functions can
be selected.
PANEL EDITING
SWITCHES
When the operator selects an access function or engineer function, several
operator switches can be used for editing:
• The MORE MESSAGES switch is also used for switch 1 and switch UP.
• The TEST DISPLAY switch is also used for switch 2 and switch DOWN.
• The MENU switch is also used for switch 3 and switch LEFT.
• The ENTER switch is also used for switch 4 and switch RIGHT.
• The ACCESS switch is also used for switch 5 and switch EXIT.