User's Manual
TM0110 Page 5 of 22 Issue 1.00
FIRE ALARM The red FIRE ALARM light comes on when any zone is in a fire alarm
condition. This light flashes 1 second on 1 second off when a new zone
fire alarm event occurs and is constant when accepted by operation of the
silence/resound sounders switch. Operation of the panel reset switch
turns this light off only if the alarm condition is removed.
FIRE OUTPUT The red FIRE OUTPUT light comes on when the monitored and non
monitored fire outputs are active.
GENERAL DISABLE The yellow GENERAL DISABLE light comes on if any zone monitoring
circuit, alarm circuit, fire output or output delays are disabled.
GENERAL TEST The yellow GENERAL TEST light comes on if the panel has one or more
zones in test mode.
MORE MESSAGES The yellow MORE MESSAGES light comes on if there are more than 2
messages available on the display.
ZONE FIRE The red ZONE fire light comes on if there is a fire on a specific zone.
ZONE FAULT The yellow ZONE fault light flashes 1 second on 1 second off on a zone
fault condition, flashes 0.5 second on, 0.5 second off if a zone is in test or
is steady on if a zone is disabled.
PANEL ACCESS The yellow PANEL ACCESS light comes on if the panel is in access level
2 and flashes 1 second on 1 second of when the panel is in access level
3.
1.4 CONTROLS
The four access levels to the panel’s controls are shown in Table 1.
Access Level Operating Level PANEL ACCESS Light Time Out Pass Code
1 Normal operation Off N/A N/A
2 User On constantly N/A 7179
3 Engineer Flashing (1 second on/off) 30 seconds 7134
4 Engineer (counter clear) Flashing (1 second on/off) N/A N/A
Table 1: Access Levels
Access Level 1 is the normal operating condition, where, with no zones disabled, the green POWER
ON light is on and all other lights are off. The TEST button, which is used to test all of the lights in the
panel display, is operative. The SILENCE BUZZER button is active, but only for faults and not for
alarm conditions. All other controls are inoperative and are only available in Access Level 2.
The panel control switches sound the panel internal buzzer when operated. If any of these switches
are operated for more than 10 seconds or are stuck in the on position, the panel indicates a fault
condition, SYSTEM FAULT light flashes 1 second on 1 second off, the internal panel buzzer sounds
intermittently and the fault output is active.