User's Manual

TM0110 Page 21 of 22 Issue 1.00
Power Supply
Mains supply voltage 230V AC +/- 10% 50/60 Hz
Internal power supply 28V DC Nominal
Output Voltage range 19V – 30V
Ripple Voltage 500 mV 10 kHz bandwidth
Total output current limited to 2.5 A
Supply and battery charger monitored YES
Batteries monitored YES
Max battery size and Type 2 Yuasa NP7-12 12V 7 Ah SLA connected in
series*
Mains Fuse 240V 3.15A (T) anti-surge
Battery fuse 2.5 A
Auxiliary 28V supply fuse 500 mA (T) anti-surge
Quiescent current (mains off) 30 mA 8 zone control panel
Alarm current (mains off) 90 mA 8 zone control panel
Maximum current to be drawn from batteries
when the mains is not present
2 A
Maximum charger output 500 mA
*Use of another battery type may invalidate the EN54 approval.
Detector Circuits
Number of circuits 2, 4, or 8
End of line capacitor value 10uF 35V (or higher) electrolytic
Max cable length per circuit 1 km
Monitored for open and short circuit YES
Monitored for detector removal YES
Detector circuit Voltage 24V DC max, 18V DC min
Maximum line resistance (each core) 22
Maximum cable capacitance 1 µF
Call point resistor value 470 to 680
Max number detectors per zone 32 (see note on page 13)
Max number of call points per zone No limit (see note on page 13)
Sounder Circuits
Number of circuits 2
End of line resistor value 6K8 5% 0.25W
Monitored for open and short circuit YES
Alarm sounder circuit voltage 24V DC max, 21V DC min