User's Manual

TM0110 Page 18 of 22 Issue 1.00
PANEL ALARM MODES
The PANEL ALARM MODES function allows the engineer to configure the panel alarm circuits.
When the panel is in an alarm state, the alarm circuits can either be steady on or sound intermittently.
There are 3 alarm modes available:
ALARM MODE 1 Alarms all steady on
ALARM MODE 2 Alarms all sounding intermittently 3 second on 3 second off
ALARM MODE 3 Alarms all sounding intermittently 3 second on 3 second off with single zone
fire condition and all steady on with more than one zone fire condition
DETECTOR LIGHT
The DETECTOR LIGHT function allows the engineer to select if detector alarm lights are steady or
flashing in alarm. The flash rate is set to 1/4 second on and 1 second off.
EDIT ACCESS CODE
The EDIT ACCESS CODE function allows the engineer to select a new 4 digit panel access code
(default 7179).
SYSTEM FAULT CLEAR
The SYSTEM FAULT CLEAR function allows the engineer to clear any standing system fault
conditions. If the SYSTEM FAULT light and GENERAL FAULT light flash 1 second on 1 second off,
a system fault condition has occurred. A system fault could occur in a brown-out condition
(microprocessor voltage supply low), system software crash or out of step, software checksum error
or system hardware fault. These fault conditions are indicated even after a panel reset. To clear
these fault conditions use SYSTEM FAULT CLEAR through the engineer menu.
PANEL DEFAULTS
The PANEL DEFAULTS menu must only be used by a competent engineer because all programmed
data is lost when used. The sequence of key codes for panel defaults has been extended for this
purpose.
This function allows the engineer to configure the panel to all its factory default settings:
All zones will be circuit type latching fire
No zones will be coincidence zones
No zones will be delayed in an alarm condition
Day time delay T1 and T2 will default to 1 second
Night mode time defaults to 18:00:00
Alarm mode 1 (all alarms steady on in alarm)
Detector alarm lights steady in the event of the detector reaching an alarm state
User access code defaults to 7179
When the panel is commissioned, the above defaults are configured into the panel.