User's Manual
TM0110 Page 17 of 22 Issue 1.00
ZONE ONE MAN TEST
The ZONE ONE MAN TEST function allows the engineer to test zone FIRE responses from one or
more zones remotely from the panel. An engineer can put the zone into test and remotely trigger a
detector or manual call point into fire. When in fire all panel alarm devices operate but the fire outputs
do not operate. After 3 seconds the alarms turn off and the panel resets automatically. When the fire
alarm condition is cleared the alarms sound twice, telling the engineer that the tested zone is now
clear.
Faults from zones in test will be ignored.
In the quiescent state a zone in test is indicated by the ZONE fault light flashing 0.5 second on, 0.5
second off and the GENERAL TEST light on.
ZONE CIRCUIT TYPE
The ZONE CIRCUIT TYPE function allows the engineer to configure any zone to be latching or non-
latching fire. This function allows the panel to interface to other fire panels or equipment where only a
fire indication is required.
COINCIDENCE ZONES
The COINCIDENCE ZONES function allows the engineer to configure 2 zones as coincidence zones,
which requires both zone alarm conditions to be active before the panel alarms and fire outputs are
operated. Zone pairs which can be configured are:
• ZONE 1 AND ZONE 2
• ZONE 3 AND ZONE 4
• ZONE 5 AND ZONE 6
• ZONE 7 AND ZONE 8
DAY DELAY ZONES
The DAY DELAY ZONES function is used to configure the zone/s in alarm which delay the alarm and
fire outputs. Zone/s not configured for day delay automatically operate the alarm circuits and fire
outputs when in alarm.
DAY TIME DELAY
The DAY TIME DELAY function is used to set the time in seconds for T1 and T2 day time timers. T1
time is set for investigating if the zone alarm is true or false. T2 time is set as a time delay for
operation of the alarms circuits and fire outputs. When a delayed zone is in alarm, T1 timer starts and
the OUTPUT DELAYS light flashes 1 second on, 1 second off. If no switch is pressed, after T1 delay
the alarm circuits and fire outputs operate. To override T1 delay, operation of the SILENCE
RESOUND ALARMS switch automatically operates the auxiliary alarms and fire outputs. If during T1
delay the SILENCE BUZZER switch is operated, T1 timer stops and T2 timer starts. If the alarm is
investigated and is false, operation of the silence/resound switch cancels T2 timer and the alarm
circuits and fire outputs do not operate. If the alarm is investigated and is true, after T2 time expires
the alarm circuits and fire outputs operate.
NIGHT MODE TIME
The NIGHT MODE TIME function is used to set the time where the panel switches from Day mode to
Night mode. In night mode no delays are active even if enabled, any alarm event will operate the
alarm circuits and fire outputs. To switch from night to day mode of operation press the ENTER
switch.