User's Manual
400 Main Street
Ashland, MA 01721
Tel.: 508-881-2000
Fax: 508-881-8920
www.kiddefiresystems.com
This literature is provided for informational purposes only. KIDDE-FENWAL, INC. assumes
no responsibility for the product’s suitability for a particular application. The product must be
properly applied to work correctly.
If you need more information on this product, or if you have a particular problem or question,
contact KIDDE-FENWAL, INC., Ashland, MA 01721. Telephone: (508) 881-2000.
K-73-06 Rev AC © 2013 Kidde-Fenwal Inc.
SmartOne and Kidde are registered trademarks of Kidde-Fenwal, Inc. LHS is a trademark of Kidde-Fenwal, Inc.
FIRE ZONE LOCATION WITH LHS
An Intelligent Linear Heat Detection System is recom-
mended for applications where fire zone location requires
zone output control for notification appliances, HVAC
control, suppression control and annunciation. In this sys-
tem, each discrete addressable LHS cable zone will
report an individual alarm to the SmartOne®-compatible
fire control panel.
Addressable LHS cable zones are created by attaching
each LHS cable zone to an Addressable Input module
(P/N 70-407008-001). Each discrete LHS cable zone
location can be displayed on the SmartOne-compatible
panel 80-character LCD display with programmable text
zone description. Up to 255 devices (any mix of devices
including smoke detectors, manual pull stations, water-
flow switches, LHS zones, etc.) can be connected to a
single SmartOne-compatible’s addressable loop.
Installing an Intelligent Linear Heat Detection System
results in substantial installation cost savings over tradi-
tional hard-wired linear heat detection systems.
Table 1: LHS Sensor Cable Specifications
Part Number:
656 ft (200 m) length roll
3,280 ft (1000 m) length roll
73-200000-011
73-201000-011
73-200000-012
73-201000-012
73-200000-003
73-201000-003
73-200000-004
73-201000-004
73-200000-005
73-201000-005
Alarm Temperature Range
145-158ºF
(63-70ºC)
180ºF
(82ºC)
220ºF
(105ºC)
350ºF
(177ºC)
452F
(233ºC)
Ambient Storage Temp.* Up to 113ºF (45ºC) Up to 158ºF (70ºC) Up to 221ºF (105ºC) Up to 392ºF (200ºC)
Min. Installation Temp. 5ºF (-15ºC) 32ºF (0ºC) -4ºF (-20ºC)
Min. Operating Temp.** -40ºF (-40ºC) -22ºF (-30ºC) -40ºF (-40ºC) -58ºF (-50ºC)
Application Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor Indoor/Outdoor
Approved Spacing 20 ft (6m) max Proximity Detection
Flame Detection 5 seconds (max) 12 seconds (max) 20 seconds (max)
Outer Jacket Material Nylon Nylon PVC FEP
Outer Jacket Color
Black
Marked H8040N
Black
Marked H8045N
Black Red White
Conductor Insulation EVA Polythene Polypropylene FEP
Conductor Color
1 Black
1 Red
1 Black
1 Black/White
1 Black
1 White
External Diameter 0.13 in. (3.35 mm) 0.13 in. (3.35 mm) 0.17 in. (4.35 mm) 0.17 in. (4.35 mm) 0.14 in. (3.5 mm)
Electrical Rating 1 Amp maximum, 110 Vdc maximum
Conductor Resistance 30.48 ohms/1000 ft. @ 68ºV (100 ohms/1000 m) @ 20ºC
Conductor Capacitance
20.21 pF/ft.
(66.32 pF/m)
25.42 pF/ft.
(83.31 pF/m)
19.96 pF/ft.
(65.48 pF/m)
17.52 pF/ft.
(57.48 pF/m)
19.22 pF/ft.
(63.07 pF/m)
Insulation Rating 1000 megohm per 3280 ft. (1000 m) after 1 minute @ 500 Vdc Minimum
Weight
10.65 lb./1000 ft.
(15.85 kg/km)
10.65 lb./1000 ft.
(15.85 kg/km)
15.25 lb./1000 ft.
(22.7 kg/km)
12.67 lb./1000 ft.
(18.85 kg/km)
14.65 lb./1000 ft.
(21.8 kg/km)
*Do not store in direct sunlight. **When not subjected to vibration.