User's Manual

- 5 -
SOLENOID, P/N 83-100034-001
An optional solenoid can be installed into the XV Control
System, just under the actuation latch. The solenoid
operates directly on the actuation latch to activate the
system. This installation allows simultaneous usage of
mechanical detection lines, or the lines can be locked
out. The solenoid includes two mounting bolts, the
bracket and a push plate which mounts onto the solenoid
body (Figure 6). The solenoid coil is 24 Vdc at 1.5 Amp
and at 70°F (21°C). Refer to Figure 7 for Release Wiring with
Terminal Type Microswitch.
When actuating the XV Control System with an optional
solenoid, a UL Compatible and Listed fire control panel
with a supervised power supply is required, such as the
Kidde AEGIS or Kidde ARIES.
Figure 6. Solenoid, P/N 83-100034-001
Figure 7. Release Wiring with Terminal Type Microswitch
Note: Where electric detection and/or actuation is pro-
vided, supervision shall be provided in accor-
dance with NFPA 72, National Fire Alarm and
Signaling Code. Alarms and indicators, along
with a supervised power source, shall be pro-
vided in accordance with NFPA 72. Electrical wir-
ing and equipment shall be provided in
accordance with NFPA 70, National Electric
Code. All installations are subject to the approval
of the Authority Having Jurisdiction (AHJ).
KEEPER PIN, P/N 60-9197108-000
The Keeper Pin (P/N 60-9197108-000) is used to prevent
actuation while installing the system.
Figure 8. Keeper Pin, P/N 60-9197108-000
ELECTRICAL LEADS
24 in. (610 mm)
MOUNTING BRACKET
(DO NOT REMOVE)
PUSH PLATE
(DO NOT REMOVE)
SOLENOID BODY
9/64 in. ALLEN SCREWS (2)
FLAG ENGAGED
BY XV
TERMINAL 2 NOT USED
OPEN TERMINAL 2
ATTACH SOLENOID LEAD TO
TERMINAL 1 OF MICROSWITCH
COMMON
TERMINAL 1
ATTACH RELEASING CIRCUIT TO
TERMINAL 4 OF MICROSWITCH
CLOSED TERMINAL 4
SPLICE SOLENOID LEAD
TO RELEASING CIRCUIT
RELEASING CIRCUIT
IN COMPATIBLE CONTROL
PANEL ( )24 VDC ONLY
XV SOLENOID
P/N 83-100034-001
24 VDC ONLY
SWITCH POSITION WHEN FLAG/CAM IS IN SET POSITIONXV
ALARM WIRES TO
SOLENOID AND/OR OTHER
DEVICES
XV
WIRE TYPE KEY
MICROSWITCH (INTERNAL)
ALARM WIRES FROM
CONTROL PANEL