User's Manual

- 4 -
SYSTEM VALVE ACTUATOR (SVA), P/N 87-120042-001
A System Valve Actuator (SVA) must be mounted to every system cylinder valve assembly (see Figure 4). The SVA
has ports for low profile tubing runs, and is also equipped with a spring loaded plunger that locks the piston in the
discharged position, ensuring complete discharge of the cylinder(s) contents.
Figure 4. System Valve Actuator (SVA), P/N 87-120042-001
HIGH-PRESSURE NITROGEN TUBING, P/N 87-120045-00X
The High-Pressure Nitrogen Tubing is used to connect the XV Control System to the SVA on all installations in which
the XV Control System is mounted to a wet or dry chemical cylinder. (see Figure 5). A 1/8-inch NPT (male) x 3/8-24 JIC
Adapter is included with the High Pressure Nitrogen Tubing.
Figure 5. External Tubing for XV Control System, P/N 87-120045-00X
Table 5. External Tubing for XV Control System
Part Number Length "A"
87-120045-001 7-1/2 in. (191 mm)
87-120045-002 24 in. (610 mm)
87-120045-003 60 in. (1524 mm)
1/8 in. NPT PLUG
(IF APPLICABLE)
5/16-18 UNC
THROUGH HOLE (TYP)
(NOT SHOWN)
PISTON IN ACTUATED
POSITION (TOWARDS
CYLINDER VALVE)
1-3/4 in.
(44 mm)
SPRING LOADED
PLUNGER
1/8 in.
NPT PORT
SVA PISTON IN
SET POSITION
1/8 in. NPT
THREAD
1/2 in. HEX,
1/4 in. 37 DEGREE
FLARE, SWIVEL
A
(END TO SEAT)
SEAT
1/8 in. NPT
(MALE) x 3/8-24
JIC ADAPTER